5
Commissioning
48
Festo – P.BE-CPX-CMAX-SYS-EN – en 2017-09b – English
5
Commissioning
5.1
Important notes on commissioning
This description provides an overview for commissioning the positioning system with the CMAX using
the Festo Configuration Tool with the CMAX plug-in.
Information about configuration of the CMAX with specific CPX nodes as well as the
description of commissioning via the CPX node
è
Communication profile description,
P.BE-CPX-CMAX-CONTROL-... .
Recommendation: Perform configuration and commissioning of the CMAX with the new
est FCT plug-in CMAX. Only the latest FCT plug-in offers comprehensive support and use
of all functions of the CMAX.
Note
Errors in the system structure and incorrectly set parameters can cause the drive to
move uncushioned to an end position. This can destroy the drive.
Before applying compressed air, set the configuration and application data correctly.
In the following cases, always perform the movement test after the compressed air
is switched on so that a defective tubing connection can be detected:
–
at the first commissioning (after installation)
–
after replacement of the drive, the displacement encoder or the proportional
directional control valve VPWP
–
after changes to the tubing connection
During operation, make sure that the permitted total load is observed.
Recommendation:
Attach corresponding warning signs to your system.
Recommendation: when commissioning with the Festo Configuration Tool:
To avoid influence by I/O signals:
Perform commissioning without bus (pull off bus line) or reset, defined to 0, the PLC
output data for the CMAX.
With use of a control block (CPX-FEC, CPX-CEC):
Switch the control block to stop!