5. Diagnostics and error handling
Festo GDCP-CMXR-C2-HW-EN 1002NH
53
5.3.1
Error codes
Possible error codes are dependent on the current operating status of the device and
summarised accordingly in the following tables. This means that a first diagnosis is
possible without reading out the status report files.
Error displays not listed are intended for the support team at Festo.
Running up errors: Errors during Power-on self-test
Error display
Cause
Action
2 – E 401
Extended boot system was not found.
Re-initialise the memory card with FCT
2 – E 402
CRC error in extended boot system.
Re-initialise the memory card with FCT
2 – E 403
Boot system not suited for HW revision.
Re-initialise the memory card with FCT
Running up errors: Errors when loading the firmware
Error display
Cause
Action
3 – E 501
Firmware package was not found
Re-initialise the memory card with FCT
3 – E 502
CRC error in firmware package
Re-initialise the memory card with FCT
3 – E 503
Firmware package not suited to HW
Re-initialise the memory card with FCT
3 – E 504
Not enough memory for the firmware
package
Re-initialise the memory card with FCT
Running up errors: Errors when initialising and starting the operating system
Error display
Cause
Action
5 – E 101
Operating system error
Re-initialise the memory card with FCT
5 – E 205
Too many peripheral modules connected
in series
Reduce the number of modules connected
in series
Error handling
More detailed information on handling the errors in your multi-axis
control system CMXR can be found in the system description.