CMSX-...-C-U-F1-...
Festo – CMSX-...-C-U-F1-... – 1506a English
45
7.6.9
Information menu (5)
The following information can be called up in the Information menu (5):
Display
Description
MENU 5 INFORM
L1 ...°
Lower limit of the initialized opening angle (semi-rotary drives)
...
Numerical value [°]
L1 IN
Bottom dead center (linear drives)
...
L2 ...°
Upper limit of the initialized opening angle (semi-rotary drives)
...
Numerical value [°]
L2 OUT
Top dead center (linear drives)
...
V1 ...k
Number of switching cycles of the fast-switching valve V1 since the last initialization
process
...k
Numerical value
1)
[1000]
V2 ...k
Number of switching cycles of the fast-switching valve V2 since the last initialization
...k
Numerical value
1)
[1000]
Ver A3.3
Firmware design of the device
3.x
Version number
1)
k for kilo (thousands)
Tab. 22
Information menu (5)
MENU
5 INFORM
*INFORM*
L1 ...°
L2 ...°
V1 ...k
...
6
3
1
2
Fig. 33
Movement in the Information menu (5)
Operation
Selection in the INFORM menu
Briefly press Add
1
Continue to the next selection
Briefly press Sub
2
Back to the previous selection
Briefly press Set
3
Back to the main menu
Press and hold Set
4
Tab. 23
Operation in the Information menu (5)
7.6.10
Initialization menu (6)
Initialization can be started or a reset executed in the Initialization menu (6). Further, current settings
can be saved as individual presettings.