ID Dx.
Name
Description
12 | 01 | 00213
(201392341)
Load change error threshold
reached
Threshold value 2 (default: error threshold)
for the load change is reached
Tab. 447 Diagnostic messages
Example
The load change counter should be reset to 0 and the following threshold values should be paramet-
erised:
–
Warning threshold for the load change counter of axis 1: 4500000 user units
–
Error threshold for the load change counter of axis 1: 90000000 user units
Parameter settings (example)
Parameters
Value
Comment
Load change
P1.1421.0.0
0
Rest axis load change to 0
Warning threshold for the load change counter
P1.1427.0.0
4500000
Load change warning threshold of axis 1
Error threshold for the load change counter
P1.14211.0.0
90000000
Load change error threshold of axis 1
Tab. 448 Parameter settings (example)
9.6.2.1
CiA402
Load change counter objects
Parameters
Index.Subindex
Name
Data type
Px.
Manufacturer-specific objects: saved basic unit for the object is effective.
1421
0x2185.01
Load change counter
SINT64
1427
0x2185.05
Warning threshold load change counter
SINT64
14211
0x2185.08
Error threshold load change counter
SINT64
Tab. 449 Objects
9.6.3
Operating hour counter
The operating hour counter records how long the 24 V logic supply of the servo drive was switched on.
Diagnostics and fault clearance
511