56
Festo — CMMT-ST-C8-1C-...-S0 — 2021-04b
Technical data
10.3
Characteristic curves
Required power reduction
Mounting clearances may be required at output currents > 4.6 A to ensure the device reaches its
specified service life. The required mounting clearances depend on the ambient temperature and the
output current.
Mounting clearances from 0 mm are possible for a device compound consisting of several servo drives
CMMT-ST. The following characteristic curves show the maximum permissible effective currents for the
lateral mounting clearances 0 mm, 3 mm, 10 mm and 15 mm.
1
2
3
4
Fig. 15: Power reduction as a function of the ambient temperature and mounting clearance
1 Mounting clearance 15 mm
2 Mounting clearance 10 mm
3 Mounting clearance 3 mm
4 Mounting clearance 0 mm
10.4
Technical data UL/CSA certification
In combination with the UL inspection mark on the product, the information in this section must also
be observed in order to comply with the certification conditions of Underwriters Laboratories Inc. (UL)
for USA and Canada.
UL/CSA certification information
Product category code
NMMS / NMMS7 (Power Conversion Equipment)
File number
E331130_Vol-3_Sec-1