6. Setting Parameters
Festo P.BE-CMMP-CO-SW-EN 0708NH
111
6.12
Analogue inputs
6.12.1
Overview
The motor controllers of the CMMP series have three analogue inputs over which, for
example, command values can be specified to the motor controller. For all these analogue
inputs, the following objects offer the possibility to read out the current input voltage
(
analog_input_voltage
) and set an offset (
analog_input_offset
).
6.12.2
Description of the Objects
Index
Object
Name
Type
Attr.
2400
h
ARRAY
analog_input_voltage
INT16
ro
2401
h
ARRAY
analog_input_offset
INT32
rw
2400
h
: analog_input_voltage (input voltage)
The object group
analog_input_voltage
supplies the current input voltage of the
respective channel in millivolts, taking the offset into account.
Index
2400
h
Name
analog_input_voltage
Object code
ARRAY
No. of Elements 3
Data Type
INT16
Sub-index
01
h
Description
analog_input_voltage_ch_0
Access
ro
PDO Mapping
no
Units
mV
Value Range
--
Default Value
--
Sub-index
02
h
Description
analog_input_voltage_ch_1
Access
ro
PDO Mapping
no
Units
mV
Value Range
--
Default Value
--