5
Setting parameters
92
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
Object 6510
h
_3A
h
: enable_enhanced_modulation
The extended sine modulation can be activated with the object enable_enhanced_modulation. It per
mits better utilization of the intermediate circuit voltage and thus about 14%-higher speeds. A disad
vantage in certain applications is that the control behaviour and smooth running of the motor can be
slightly worse at very low speeds. write access is possible only when the output stage is switchedoff. To
accept the change, the parameter set must be backed up and a reset performed.
Sub-Index
3A
h
Description
enable_enhanced_modulation
Data Type
UINT16
Access
rw
PDO mapping
no
Units
–
Value Range
0, 1
Default Value
0
Value
Meaning
0
Extended sine modulation OFF
1
Extended sine modulation ON
Activation of the extended sine modulation is only effective after a reset. As a result, the
parameter set must be saved (save_all_parameters) and then a reset performed.
Object 6510
h
_31
h
: power_stage_temperature
The temperature of the output stage can be read via the object power_stage_temperature. If the tem
perature specified in object 6510
h
_32
h
(max_power_stage_temperature) is exceeded, the output
stage shuts off and an error message is output.
Sub-Index
31
h
Description
power_stage_temperature
Data Type
INT16
Access
ro
PDO mapping
yes
Units
°C
Value Range
–
Default Value
–