![Festo CMMP-AS-***-M0 Series Manual Download Page 108](http://html1.mh-extra.com/html/festo/cmmp-as-m0-series/cmmp-as-m0-series_manual_2283119108.webp)
5
Setting parameters
108
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
Index
60FB
h
Name
position_control_parameter_set
Object Code
RECORD
No. of Elements
4
Sub-Index
01
h
Description
position_control_gain
Data Type
UINT16
Access
rw
PDO mapping
no
Units
256 = “1”
Value Range
0 … 64*256 (16384)
Default Value
102
Sub-Index
02
h
Description
position_control_time
Data Type
UINT16
Access
ro
PDO mapping
no
Units
μs
Value Range
0
Default Value
0
Sub-Index
04
h
Description
position_control_v_max
Data Type
UINT32
Access
rw
PDO mapping
no
Units
speed units
Value Range
0 … 131072 min
-1
Default Value
500 min
-1
Sub-Index
05
h
Description
position_error_tolerance_window
Data Type
UINT32
Access
rw
PDO mapping
no
Units
position units
Value Range
1 … 65536 (1 R)
Default Value
2 (1/32768 R)