5
Setting parameters
102
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
Sub-Index
2F
h
Description
max_motor_temperature
Data Type
INT16
Access
rw
PDO mapping
no
Units
°C
Value Range
20 … 300
Default Value
100
Object 60F6
h
: torque_control_parameters
The data of the current controller must be taken from the parametrisation software. The following cal
culations must be observed:
Amplification of the current controller must be multiplied by 256. With an amplification of 1.5 in the
Current Regulator menu of the parametrisation software, the value 384 = 180
h
must be written in the
object torque_control_gain.
The current controller time constant is specified in the parametrisation software in milliseconds. To
transfer this time constant into the object torque_control_time, it must previously be converted into
microseconds. With a specified time of 0.6 milliseconds, the corresponding value 600 is entered in the
object torque_control_time.
Index
60F6
h
Name
torque_control_parameters
Object Code
RECORD
No. of Elements
2
Sub-Index
01
h
Description
torque_control_gain
Data Type
UINT16
Access
rw
PDO mapping
no
Units
256 = “1”
Value Range
0 … 32*256
Default Value
3*256 (768)
Sub-Index
02
h
Description
torque_control_time
Data Type
UINT16
Access
rw
PDO mapping
no
Units
μs
Value Range
104 … 64401
Default Value
1020