2 IO-Link
Festo – GDCP-CMMO-ST-LK-C-HP-EN – 2017-05b – English
13
2.3
Configuration IO-Link master
To create the IO-Link connection, configure the motor controller in the IO-Link master.
Steps for configuration of the IO-Link master
è
documentation on the used configuration
program (CODESYS, TIA-Portal, STEP 7, ...).
The IODD files include all necessary information on configuration:
IODD files
Device profile
Festo-CMMO-ST-C5-1-LKP_FHPP-xxxxxxxx-IODD1.1.xml
FHPP standard (8 I/O bytes)
Festo-CMMO-ST-C5-1-LKP_FHPP_and_FPC-xxxxxxxx-IODD1.1.xml
FHPP st FPC
(16 I/O bytes)
(xxxxxxxx = date)
Tab. 2.2
IODD files
The motor controller supports the IO-Link specification V1.1 with the following characteristics:
– Cyclical IO-Link data 8 or 16 I/O bytes.
– Device-specific errors and warnings are reported to the IO-Link master through the “Event manage
ment”.
– SIO mode is not supported.
– Transmission rate 230.4 KBaud.
– No support of the parameter server of the IO-Link master (2048 bytes for parameters of the motor
controller are not sufficient).
The upload and download of all parameters to the controller can be implemented via EFPC with
appropriate functional modules or function blocks
è
Current IODD files, functional modules or function blocks
è
www.festo.com/sp