5
Commissioning
88
Festo – GDCP-CMMO-ST-EA-SY-EN – 2017-05c – English
5.3.6
Completing commissioning
Recommendation: check temperature characteristics
Check the long-term characteristics of the output stage temperature with FCT.
In the FCT, the temperature characteristics are displayed for a period of 30 minutes (FCT online
tab“Monitoring”).
Recommendation: disable“Automatic saving” option
Under FCT [...][Controller] [I/O Configuration] disable the automatic saving of taught positions in the
Flash memory
Creating a backup file
The creation of a backup file (Restore file) makes it possible:
– to parameterise a few motor controller quickly when replacing a device
– to commission several actuators quickly with the same parameterisation
– to restore the parameterisation of the motor controller in the event of data loss
When creating a backup file, the complete parameter file is loaded from the motor controller and is
saved on the PC. If no valid parameter file is present in the controller, the default parameter file is
loaded and saved.
1. Adopt device control on the web browser (reset controller enable)
2. With <Store> (below the table of sets of commands) the sets of commands can be saved perman
ently to the motor controller.
3. Interrogate parameter file from the permanent memory of the controller with <Upload parameter set
to CMMO>
4. Save parameter file *. fpf to data carrier via the displayed Windows dialogue.
Transferring a backup file
To transfer a backup file from the PC to the motor controller:
Write the parameter file to the permanent memory of the controller with <Download parameter set
to CMMO>.
After the download: reboot the motor controller (Power on/off ).
Enabling password protection
Password protection protects the motor controller from unauthorised modifications and prevents con
trolling access to the actuator via FCT or web server:
1. Adopt device control on the web browser (reset controller enable)
2. Enter a password (website“Parameters”: Password):
– Maximum length of password: 16 characters
– Permitted characters: aZ, AZ, 09 !"#$%&'()*+,./:;<=>?@[\]^_{|}~
The password is case-sensitive.
3. Save the password with <Apply>.
The password is permanently stored in the motor controller.
To create a compatible parameter file for firmware
.
V1.1.2.4 all current parameters are
also saved in the parameter file of the controller with <Apply>. For further information
about password protection
è