Commissioning
Festo – GDCP-CMMO-ST-EA-SY-EN – 2017-05c – English
103
5.5.6
Execute command records (RECORD)
To initiate a command record, in addition to ready status, the following conditions must be satisfied:
the actuator is referenced (DOUT REFERENCED = 1)
The inputs for starting the command records (RECORD 1 to 7, REF) are flank-controlled. After the flank
change 0
è
1 the signal must remain in place until the action triggered by it has been completed. If the
signal is reset, the actuator is braked down to a stop using the parameterised braking ramp (decelera
tion record). If the actuator comes up against a physical stop, it uses the parameterised nominal
torque to press against the stop until the input is disabled.
Start/Stop sequence with record switching
–
Start record: by enabling an input RECORDx the command record is addressed and the order is
started. The input RECORDx must remain enabled until the specified target has been reached.
–
Stop record: during execution of the order, if input RECORD x is disabled, the actuator is slowed
down to a complete stop by the parameterised record delay. The order is discontinued. The output
RECORDx is not enabled.
–
Record changeover: execution of the record is interrupted during selection of the following record
and the following record is executed immediately without a stop. The output is not set. Note about
programming: first, enable input of following record, then disable input of interrupted record.
–
Target reached (Motion complete):
the actuator is in the position window for the parameterised rest time. The corresponding output
RECORDx REACHED is set. The output remains set while the actuator remains at the target positon
(even if the input is reset).