INSTALLATION
Antifreeze system, antifreeze fluids, additives and inhibitors
When necessary, antifreeze fluids, additives and inhibitors can be used only if the manufacturer of such fluids or additives guarantees that they are suitable and do not
cause damage to the exchanger or other components and/or materials of the boiler/heat pump and system. Do not use generic antifreeze fluids, additives or inhibitors
that are not specific for use in heating systems and compatible with the materials of the boiler/heat pump and system.
System water characteristics
The heat pumps are suitable for installation in heating systems with non-significant entry of oxygen (ref. systems “case
I” EN14868). A physical separator (e.g. plate heat exchanger) must be provided in systems with continuous entry of oxygen
(e.g. underfloor systems without antidiffusion pipes or open vessel), or intermittent (less than 20% of system water content).
The water within a heating system must have the characteristics required by UNI 8065, and comply with laws and regulations
in force and the provisions of EN14868 (protection of metallic materials against corrosion).
The filling water (first filling and subsequent replenishment) must be clear, with hardness below 15°F and treated with suitable
chemical conditioners against the initiation of corrosion, that are not aggressive on metals and plastics, do not develop gases
and, in low-temperature systems, do not cause proliferation of bacterial or microbial masses.
The water in the system must be periodically checked (at least twice a year during the season when the systems are used,
as required by UNI8065) and have: possibly a clear appearance, hardness below 15°F for new systems or 20°F for existing
systems, pH above 7 and below 8.5, iron content (Fe) below 0.5 mg/l, copper content (Cu) below 0.1 mg/l, chloride content
below 50mg/l, electrical conductivity below 200 µs/cm, and must contain chemical conditioners in a concentration sufficient
to protect the system for at least one year. Bacterial or microbial loads must not be present in low temperature systems.
Only use conditioners, additives, inhibitors and antifreeze liquids declared by the producer suitable for use in heating systems
and that do not cause damage to the heat exchanger or other components and/or materials of the boiler and system.
Chemical conditioners must ensure complete deoxygenation of the water, contain specific protection for yellow metals (cop-
per and its alloys), anti-fouling agents for scale, neutral pH stabilizers and, in low-temperature systems, specific biocides for
use in heating systems.
Recommended chemical conditioners:
SENTINEL X100 and SENTINEL X200
FERNOX F1 and FERNOX F3
The unit is equipped with a frost protection system that activates the heat pump in heating mode when the system delivery
water temperature falls below 4°C. The device is not active if the power and/or gas supply to the unit is turned off. If neces-
sary, for system protection use a suitable antifreeze liquid that meets the same requirements as set out above and provided
for by Standard UNI 8065.
In the presence of adequate chemical/physical system and feed water treatments and related high cyclicity controls able to
ensure the required parameters, for industrial process applications the product can be installed in open-vessel systems with
vessel hydrostatic height able to ensure compliance with the minimum operating pressure indicated in the product technical
specifications.
The presence of deposits on the indoor unit exchange surfaces due to non-compliance with the above requirements
will involve non-recognition of the warranty.
Water filter
A water filter must be installed at the entrance of the unit.
The unit is supplied as standard with two square taps. The tap with a blue handle is equipped with a filter (which can be disassembled by unscrewing the rear fitting)
and therefore acts as an interception tap and a water filter; this tap must be mounted on the system return connection (see part.10 “fig. 6 - dimensional data and
connections” on page 11). The tap with red handle must be mounted on the system delivery connection (see part 11 “fig. 6 - dimensional data and connections” on
page 11).
Summary of Contents for OMNIA HYBRID C
Page 34: ...34 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU 7 2 Menu structure ...
Page 35: ...35 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU DHW mode is setting OFF ...
Page 36: ...36 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU ...
Page 51: ...51 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU ...
Page 53: ...53 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU U ...
Page 100: ...100 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Principle scheme ...
Page 101: ...101 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Electronic heat pump board ...
Page 102: ...102 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Wiring board ...
Page 113: ...113 EN Cod 3541T090 Rev 00 06 2019 ...
Page 114: ...114 EN Cod 3541T090 Rev 00 06 2019 ...