Series 27000

Horizontal DETECT-A-FIRE

®

Units

Installation Instructions

12.02.D

®

INSTALLATION

Figure1: Surface Mount Units

Series 27020-1 and 27021-1

Model 

Number

Contact 

Operation on 

Temperature Rise

Electrical Rating 

(Resistive Only)

27020-0

Opens

5.0 Amps 125 VAC

27020-1

27021-0

Closes

5.0 Amps 126 VAC
0.5 Amps 125 VDC
2.0 Amps 24 VDC
1.0 Amps 48 VDC

27021-1

LOCATION

DETECT-A-FIRE detectors are precision temperature sensors.
They must be mounted in an area (normally a ceiling) so that:

1. The detector spacing complies with both system 

requirements and requirements of the agency having 
local jurisdiction.

2. The thermal air path to the shell is not obstructed.

Spacing per UL, FM, and UL of Canada is shown in Table 1.
Distances given are for between units on smooth ceilings.  
Distances from partitions or walls are half that shown.  
To assure that all spacing requirements are met, consult 
the authority having local jurisdiction.

MOUNTING

DETECT-A-FIRE units are not position sensitive.  Horizontal 
and vertical detectors refer to the most common mounting 
configurations for that unit.  However, each type can be 
mounted either horizontally or vertically depending on the 
application and installation requirements.

*Although incandescent lamps are considered resistive, their inrush 
current is 10 -15 times their steady current. Do not exceed ratings.

°

Setting

°

F

Tolerance

Spacings (in feet)

RTI

Color
Coding

UL

ULc

FM

140

+7/-8

50

50

20

Quick

Black

160

+7/-8

25

25

20

Quick

Black

190

+7/-8

50

50

25

Fast

White

210

+7/-8

25

50

25

Fast

White

225

+7/-8

25

50

25

Fast

White

275

+10

25

50

25

Fast

Blue

325

+10

50

50

25

Fast

Red

Table 1: Model Number 27020*, 27021

These detectors are provided with a surface mount adaptor
which may be mounted on a ceiling or to an outlet box.   
However, if the adaptor is direct ceiling mounted, CIRCUIT 
VOLTAGE MUST BE LIMITED TO 30 VOLTS.

The Canadian Electrical Code, Part 1, requires that these 
devices be installed, mounted to an approved outlet box 
and connected to Class 1 wiring.  Surface mount units shall 
be used only in this manner for Canadian approval.

For direct ceiling mount, proceed as follows:

1. The knockouts are located on the side of the surface 

mount adaptor.  Remove appropriate knockouts and 
install rubber grommets.  

2. Mount adaptor to solid ceiling surface through slotted holde in 

adaptor mounting brackets.  Supplied insulator gasket should
be placed between ceiling and adaptor.  Adaptor may be 
rotated to position detector.

3.  Run system wiring through rubber grommets and connect 

to terminals on detector per Figure 3 observing applicable 
electrical codes.

4. Mount detector to adaptor with two #8-32 screws supplied.

For optional outlet box mount, proceed as follows:

1. Bend the mounting brackets on the supplied adaptor to fit 

standard 4-including outlet box.

2. Mount adaptor to solid ceiling surface through slotted holes in 

adaptor mounting brackets.  Supplied insulator gasket should 
be placed between ceiling adaptor.  Adaptor may be rotated to 
position detector.

Page 1                Horizontal DETECT-A-FIRE

®

Units

1-800-FENWAL-1            www.fenwalcontrols.com

* 27020 is a normally closed device and does not meet the 

requirements of NFPA-72 for use as an initiating device.