background image

FEMA ELECTRÓNICA . Series S . S40-P

7

Alarm 1

Setpoint

Hysteresis

Setpoint 2

Active

Alarm type

Alarms

Activation delay

Deactivation delay

1.10 Configuration menu (cont.)

The ‘

Alarms

’ (‘

ALr

’) menu configures the independent activation of 

up to 2 relay outputs (or transistor or control SSR), installed with the 

R1 (or T1 or SSR) optional modules 

(see section 2.1)

For outputs up 

to 4 relays, see special modules R2 and R4 at section 

2.8

The alarm 

states are indicated in the front display with leds marked as ‘1’ and 

‘2’.

To configure an alarm, enter into the alarm menu (‘

ALr1

’ or ‘

ALr2

’) 

and configure the following parameters :

• select ‘

Active

’ (‘

Act

’) to ‘

on

• at ‘

Alarm type

’ (‘

TypE

’) select the alarm acting as a maximum 

type  alarm  (‘

MAX

’)  or  a  minimum  type  alarm  (‘

MIn

’).  The  maxi

-

mum type alarm (or minimum type alarm) activates when the dis

-

play value is higher (or lower) than the setpoint value.

• at ‘

Setpoint

’ (‘

SEt

’) enter the value for the alarm activation point

.

 

This parameter is eligible for configuration through the ‘

Fast access

’ 

menu 

(see section 1.10.6).

•  configure  the  hysteresis  value  at  ‘

Hysteresis

’  (‘

hySt

’).  The  hys

-

teresis applies to the deactivation process of the alarm. The alarm 

deactivates when the reading has passed the setpoint value plus 

the hysteresis value. Hysteresis helps to avoid repetitive switching 

of the alarm relays, due to fluctuating input signals around the set

-

point.
• at ‘

Activation delay

’ (‘

dEL.0

’) configure the delay to apply before 

alarm activation. The activation delay starts counting when the set

-

point value is passed. Value from 0.0 to 99.9 seconds.

• at ‘

Deactivation  delay

’  (‘

dEL.1

’)  configure  the  delay  to  apply 

before alarm deactivation. The deactivation delay starts counting 

when the setpoint value plus the hysteresis value, is passed. Value 

from 0.0 to 99.9 seconds.
• to work with ‘windowed alarms’ (see graphical example below) 

activate ‘

Setpoint

2

’ (‘

SEt2

’) to ‘

on

’ and then configure the desired 

second setpoint value. Second setpoint must always be higher in 

value than the first setpoint.
• the ‘

Relay inverted

’ (‘

r.Inv

’) parameter inverts the normal relay 

connections. When set to ‘

on

’ the relay will be active when alarm is 

inactive. For security applications where an inactive relay controls 

the shutdown of the system.
•  the  ‘

Locked alarm

’  (‘

A.Lck

’)  parameter  disables  the  automatic 

deactivation of the alarm. Alarm deactivation must be performed 

manually, by pressing the ‘LE’ front button 

(see section 1.10.10)

1.10.3 Alarms

Reading

Time

setpoint

hysteresis

Alarm as maximum, 

 

no hysteresis, no delays

on

off

Time

activation 

delay

on

off

deactivation 

delay

Time

Alarm as maximum, 

 

with hysteresis and delays

on

off

Time

Alarm as minimum, 

 

no hysteresis, no delays

Reading

Time

Setpoint 2

Setpoint 1

Alarm as minimum,

 

with double setpoint,

 

no hysteresis, no delays

on

off

Time

Relay inverted

Locked alarm

Summary of Contents for S40-P

Page 1: ...linearization fast access to alarm setpoints tare function on power up function measure function configurable reading brightness Universal AC and DC power Up to 2 optional modules for output and contr...

Page 2: ...hold for test break applications see section 1 10 4 Multiple display filters memory for maximum and minimum reading password protection 5 brightness levels 1 1 How to order Index 1 Panel meter S40 P...

Page 3: ...connections Button UP Logo Alarms Units Button SQ Button LE Configuration menu see section 1 10 Fast access see section 1 10 6 1 6 Mechanical dimensions mm Signal see section 1 5 Jumpers see section...

Page 4: ...Ranges Accuracy Zin Max signal overload Offset drift span drift includes offset drift 4 20 mA 0 05 FS 11 Ohm 100 mA permanent 10 ppm C 25 ppm C 0 10 Vdc 0 05 FS 932 KOhm 100 Vdc permanent 10 ppm C 25...

Page 5: ...Key LE 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the chang...

Page 6: ...ed on the field providing a fast and easy way to compensate offset signals To operate the Field correction F cor function for the offset cor rection generate the minimum input signal and access the Fi...

Page 7: ...e alarm relays due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when the set po...

Page 8: ...ory of maximum MAX function displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eligible for configuration through the Fast access menu see...

Page 9: ...at the front of the instrument gives access to a list of functions configurable by the operator See section 1 8 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP...

Page 10: ...rE menu allows to operate the instrument for load cell and weight applications The tare function assigns the actual input signal value to a reading of 0 Kilos by adding an inter nal offset It does not...

Page 11: ...menu key SQ The fast access menu is not password pro tected 1 10 12 Function Password At the Brightness LIGh menu select the light intensity for the front leds With this function it is possible to ada...

Page 12: ...on 1 10 for a description of each menu entry Scaling Input low Display low Input high Display high Alarm 1 Setpoint Hysteresis Setpoint 2 Active Alarm type Activation delay Deactivation delay Left zer...

Page 13: ...ng Activate Reset Number of segments Value 2 to 20 Input 0 Display 0 Input 1 Display 1 On power up Delay Tare Seconds Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configurati...

Page 14: ...el only You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock the lower clips marked with B...

Page 15: ...ay 0 seconds Tare off Key LE no function Excitation voltage 20 Vdc Password off Brightness 3 clean by using a humid rag and do NOT use abrasive products such as alcohols solvents etc General recommend...

Page 16: ...t 1 Power Signal A B C A B C The R1 module provides 1 relay output to to install at digital panel meters from Series S up to a maximum of 2 relays in a single meter Note for more than 2 relays per ins...

Page 17: ...ayed installation as it does not require soldering or special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more inform...

Page 18: ...uration Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manual_i pdf Protocol Modbus RTU Functi...

Page 19: ...up to 31 modules Frames codified in represent able ASCII characters codes 32 to 255 directly visible using hyper terminal or similar programs Access to display values alarm status memory of maximum a...

Page 20: ......

Reviews: