TST
Startup
WUI
FEIG ELECTRONIC GmbH
Page 11 of 20
WUI_Inbetriebnahme2_GB.doc
5
Putting into operation
1. Move the barrier to ca. 10 cm before the closed position with the
À
DOWN key.
IMPORTANT
Distance is very much dependent on the type of barrier and the speed, increase the
value for fast gates.
If the movement direction is wrong, the motor rotating field is incorrect: switch off the control
system and change 2 motor connections.
2. Set the bottom limit switch so that it just activates.
IMPORTANT Limit switch in the end positions must not be run over!
3. Move the barrierto ca. 10 cm before the open position with the
¿
UP key.
IMPORTANT
Distance is very much dependent on the type of barrier and the speed, increase the
value for fast gates.
4. Set the top limit switch so that it just activates.
IMPORTANT Limit switch in the end positions must not be run over!
5. If required for the type of barrier: set the top and bottom EMERGENCY limit switches.
)
Connect N.C. contacts e.g. in the safety circuit in series with thermopile.
6. Go to parameterisation mode by pressing the
Å
STOP and
¿
UP keys and select parameter P.980
"Service Mode", open this and set parameter value "2" to "0" (automatic mode)
7. Leave the parameterisation mode by pressing the
Å
STOP key for a long time (3 sec.).
8. If necessary correct the OPEN and CLOSED limit switch positions by fine adjustment of the stop
positions in automatic mode.
WARNING
In order to avoid unintended operation of the barrier, only carry out the
adjustment of the limit switches when EMERGENCY STOP is pressed or the control system is
switched off !
9. Barrier can now be operated in automatic mode.