10.2
… with mechanical limit switches
1.
Press the
CLOSE key to move the door to a distance of approx. 50 cm from the closed position.
If the door does not move, the motor lacks power. With the aid of the boost (performance
increase at low speeds) the motor can be supplied with an increase in power.
(see Chapter 10.5), if necessary, check that the brake was released.
The distance depends to a large extent on the door type and the speed; increase this value
for fast moving doors.
If the door moves in the incorrect direction: incorrect motor rotary field, turn off controller
and reverse the 2 motor connections.
2.
Adjust the lower pre-limit switch so that it just trips.
3.
Press the
CLOSE key to move the door to a distance of approx. 10 cm from the closed position.
The distance depends to a large extent on the door type and the speed; increase this value
for fast moving doors.
4.
Adjust the lower pre-limit switch so that it just trips.
Do not travel past the limit switch at the limit positions!
5.
Press
OPEN key to move the door to approx. 50 cm from the opened position.
If the door does not move, the motor lacks power. With the aid of the boost (performance
increase at low speeds) the motor can be supplied with an increase in power.
(see Chapter 10.5), if necessary, check that the brake was released.
The distance depends to a large extent on the door type and the speed; increase this value
for fast moving doors.
6.
Adjust the upper pre-limit switch so that it just trips.
7.
Press
OPEN key to move the door to approx. 10 cm from the opened position.
The distance depends to a large extent on the door type and the speed; increase this value
for fast moving doors.
8.
Set upper limit switch so that it just trips.
Do not travel past the limit switch at the limit positions!
9.
If required by the door type: adjust upper and lower EMERGENCY limit switches.
Connect the NC
contacts, e.g. the safety circuit, in series with thermo pill.
10.
By pressing the
STOP key and
OPEN key to enter parametrization mode and select
Parameter P.980 "Service Mode", open and set parameter value "2" to "0" (Automatic mode)..
11.
Correct limit switch positions for door OPEN and door CLOSE as needed by fine adjustment of the
limit positions in automatic mode.
To prevent unintentional movement of the door, only adjust the limit switches when the
emergency stop is activated or the controller is switched off!
12.
The door may now be operated in automatic mode.