8
Basic settings
To put the controller into operation, please follow the steps outlined in these instructions.
8.1 Automatic query of basic data
If the controller is not already preconfigured by the door manufacturer, the following parameters are queried
automatically:
The DIP switch must have been turned on (see position DIP-switch figure Figure 34: DIP
switch position) so that the controller can query parameters automatically.
If DIP switch is not turned on and the basic parameters not set, error code F.090 is displayed.
The controller uses indicator "-1" or "-" in the display as a flag that the acquisition of this parameter
must be queried.
The basic data does not require changes when they were previously retrieved and set
automatically.
For operating the controller, see chapter 7
General operating instructions to set parameters
Positioning system P.205
The limit switch system in use must be set using Parameter P.205.
P.205: 0000 = Mechanical limit switches Version 1 (Figur 21: Connecting cam switches)
P.205: 0001 = Mechanical limit switches Version 2 (limit switches and pre-limit switches are normally
closed)
P.205: 0300 = Absolute encoder DES-A (GfA)
P.205: 0700 = Absolute encoder DES-B (Kostal)
P.205: 0800 = Absolute encoder TST PD / TST PE (FEIG)
P.205: 0900 = Timer limit switches