12 Messages
12.1 Error messages
Faults can be acknowledged provided they are not reset automatically.
The cause of the fault must be resolved first before the corresponding message is acknowledged.
Alternatively the
the STOP button can also be kept pressed for approx. 5 seconds.
No.
Description
Possible reason for error
F.000
Door position too far up
• Too small a parameter value for upper emergency limit switch → increase
P.239
• Upper limit switch range (limit switch band) too small → increase P.233
• Mechanical brake defective or improperly set
F.005
Outside door position too far down
• Too small a parameter value for lower emergency limit switch → increase P.
229
• Lower limit switch range (limit switch band) too small → increase P. 223
• Mechanical brake defective or improperly set
F.020
Run time exceeded (during opening, closing or
deadman)
• C
urrent motor run time has exceeded set maximum run time (P.410
(Opening), P.415 (Closing), P.419 (Deadman move)), door may be sticking or
is blocked.
• Door is blocked
• If using mechanical limit switches, one may not have tripped
F.021
Emergency opening wrong testing
• The max. a
llowed run time (P.490) during testing has exceeded
• Call service hotline
F.030
Lag error (position change of the door is less than
expected)
• door or motor is blocked
• insufficient power for providing necessary torque
• too little speed
•
mechanical limit switch was not left or is defective
• Incremental or absolute encoder shaft is slipping
• wrong positioning system selected (P.205)
• one motor phase is missing
• the brake does not release
• Settings of the failure detecting time are not
correct (P.430 or P.450)