Page 7 of 40
(4)
GENERAL ELECTRICAL & GROUNDING
DANGER:
Improper or faulty hookup of electrical components in the display case can result
in severe injury or death.
4.1
CORD CONNECTED
All standard models are supplied with a power cord that is properly sized to the amperage
requirements of the case. See the electrical data plate located on the rear left interior of the case for
the proper circuit size for each case.
The cord is factory installed protruding from the bottom rear corner of the case.
A separate circuit for each display case is required to prevent other appliances on the same circuit from
overloading the circuit and causing malfunction.
4.2
PERMANENT CONNECTED (OPTION)
Only a licensed electrician must perform all case electrical connections.
All electrical wiring hookups must be done in accordance with all applicable local, regional, or national
electrical standards.
A separate circuit for each display case is required to prevent other appliances on the same circuit from
overloading the circuit and causing malfunction.
The electrical service must be grounded upon installation.
See the electrical data plate located at the rear of the case for proper circuit size and wire ampacity.
The electrical connection box is accessible from the rear of the case with rear grill removed.
FIELD CONNECTION BOX
POWER CORD OR
CONDUIT CONNECTION
HOLE (7/8"
O
)
REAR BASE
PANEL
(6) REAR BASE
PANEL SCREWS