CONDITION
Unit Noisy
(Refrigerated Only)
Close proximity to the counter, vaulted ceilings, tile and overall
open floor plan as well as grouping equipment together can all
amplify unit
“noise”
Check that the condensing coil is not restricted.
If equipped, check the condenser air filter.
Check the evaporator and condenser fan blades are not hitting
anything.
Check panels for loose fasteners and bent panels that can allow
for vibration.
Check refrigeration lines and condensing unit for vibration.
Check compressor for any abnormal noises.
(Hot Deli Only)
Check circulation fan and blade.
Lights Not Working
Check that the light switch is on.
Shelf lights – lamp cord must be fully seated into receptacle,
gently tap them in with a
rubber mallet if needed to make full contact. Check that the lamp
cord is plugged into the end of the LED light strip. – Replace light
if necessary.
Check power AC input voltage at LED driver.
Check to DC output voltage at LED driver.
If no output, disconnect output from unit wiring harness and try
again as LED driver will put itself into protect mode if output
harness has a short. – Replace driver if necessary.
(Hot Deli Only)
If none of the incandescent lights are working, check the 10A
lamp fuse located on the rear of the case next to the circulation
fan switch.
Check to see that
all
light bulbs are the proper wattage/voltage
and are working as the light bulbs also throw heat into the case.
(
120V, 60W coated bulbs only
unless otherwise specified 230V)
Note:
Even though some models are supplied 208V – 240V due
to the overall amp draw, but the wells are split between L1 to
Neutral and L2 to Neutral and the circuitry inside the unit is still
120V internally unless outside of the U.S.A.
*** DO NOT CONVERT TO LED BULBS AS THE CASE WILL N
O T RE ACH TEMPERATURE ***
NOISE AND INCANDECENT LIGHTS
NEW BAKERY AND SERIES 90
HOT DELI
5