33
Configuring Informers Using the Web Interface
Setup, Program, and User Manual
Federal Signal www.fedsig.com
If the configuration details are lost or changed incorrectly and it becomes necessary
to restore the Informer to factory default settings, perform a Power-On Factory Default
procedure.
Restoring the Informer-IP and I-IPW to Factory Default
The Informer-IP and I-IPW can be restored to the factory default by either using the web
pages or the RESET button.
Using the Web Pages
To restore the configuration to the factory default by using the web pages:
1. Navigate to the IP address of the Informer using a web browser and log in.
2. Select Factory Default. Include or exclude Network Settings.
3. Click Apply to restore your settings to the factory defaults.
4. Reboot the device for the changes to take effect.
Using the RESET Button
To restore the configuration to the factory default by using the RESET button:
1. Remove power from the Informer.
2. Press and hold down the RESET button.
3. Apply power while holding down the RESET button until the Power and Test LEDs
begin to blink, confirming that the default configuration has been loaded.
You need to re-enter all local configuration settings before placing the Informer into
service.
Restoring the Informer100, I-IP15, I-IP2, and I-IPSIU to Factory Default
The Informer100, I-IP15, I-IP2, and I-IPSIU can be restored to the factory default by either
using the web pages or Factory Default Jumper.
Using the Web Pages
To restore the configuration to the factory default by using the web pages:
1. Navigate to the IP address of the Informer using a web browser and log in.
2. Select Factory Default. Include or exclude Network Settings.
3. Click Apply to restore your settings to the factory defaults.
4. Reboot the device for the changes to take effect.
Using Factory Default Jumper
To restore the configuration to the factory default using the factory default jumper
1. Apply power to the Informer for at least 60 seconds to allow it to boot.
2. Short JP11 on the control board for 10 seconds, and then remove the short.
3. Wait 60 seconds for the Informer to reboot with the factory default settings.
You need to re-enter all local configuration settings before placing the Informer into