2. SELECTING INSTALLATION LOCATION
Select an installation location that satisfies the following conditions, with ease of maintenance and inspection, service
life of the instrument, and assurance of reliability taken into consideration.
CAUTION
(1) A place where ambient temperature and humidity are as follows:
Flow transmitter (FSH):
−
10 to
+
50
°
C, 90%RH or lower
Detector (FSW):
−
20 to
+
80
°
C, 100%RH or lower
(2) A place not subject to direct sunlight or weather
(3) A place provided with space for daily inspection and wiring work
(4) A place not subject to radiant heat from a heating furnace, etc.
(5) A place not in an atmosphere of corrosive or explosive gas
(6) A place not subject to flooding
(7) A place not subject to vibration, dust, or moisture
2.1. Flow transmitter
Allow space of 100 mm or more between the flow transmitter and the surrounding walls. Allow sufficient space for
opening of the front cover for maintenance.
Allow sufficient space for wiring at the bottom of the case.
O P
E
N
244mm
100mm
or more
245mm
348mm