CAUTION 

WARNING 

 

 

                                   

Magnetic Starter with pushbuttons

 

                                     

 

 
 
 
For details regarding specifications, see the catalog.

 

 

Safety Precautions 

To ensure proper use of the product, be sure to read this manual and the 

other attached documents carefully before starting installation, operation, 

maintenance  and  inspection.    Within  this  instruction  manual,  safety 

precautions  are  ranked,  in  order  of  importance,  as  either“Warning”  or 

“Caution”. 

Incorrect  handling  of  the  device  may  result  in  death  or 

serious injury.   

Incorrect handling of the device may result in minor injury 

or physical damage. 

Under  certain  conditions,  improper  operation  may  result  in  serious  injury 

and/or damage even if it is labeled only as “Caution”. Every item indicated 

by either “Warning” or “Caution” should be considered significant. Be sure 

to give particular care to those items. 

 

WARNING

 

  Do not touch the product or approach it when power connected. 

Electric shock or burns may result. 

  Turn  off  the  power  before  starting  maintenance  or  inspection. 

Failure to do so may result in electric shock. 

● 

Turn  off  the  power  supply  of  main  and  control  circuit  before 

opening the cover.

 

 

CAUTION

 

For  wiring,  select  wire  size  suitable  for  the  applied  voltage  and 
current. Burns may result. Tighten wires with the tightening torque 
specified in the instruction manual. Failure to do so may result in 
fire or burns. 

Do not touch the product immediately after the power is turned off. 
As it may still be hot, burns may result. 

Treat the product as industrial waste when discarding.

 

 

1. Unpacking 

(1)

 

Check that the type, coil voltage, contact arrangement and thermal 

overload relay ratings and applicable capacity match the requested 

specifications. The magnetic starter type is indicated on the package. 

The coil voltage and thermal overload relay ratings are shown on the 

inner side of the cover. 

(2)

 

Make sure that no parts have been lost or damaged. 

2. Storage 

Store the unit in the packing box. Do not store the packing box in a 

location subject to high temperature, high humidity, corrosive gas, or 

direct sunlight. 

3. Mounting

 

(1)

 

Mount in a dry, clean and stable location.   

(2)

 

Mounting on a vertical surface. The product must not incline more 

than 15゜. (Fig.1) 

(3)

 

Use two(Fig.2) or four(Fig.3) mounting holes. 

4. Connection 

  Connectable wire size and proper tightening torque 

Terminal 

FJ-B09WP 
FJ-B12WP 
FJ-B18WP 

FJ-B25WP 
FJ-B32WP 

Main circuit /   
            Control circuit 

Main circuit /   

Control circuit 

Direct 

Solid / Stranded 

[mm

2

0.75

1.5 / 0.75

1.5 

1.0

4.0 / 0.75

1.5 

Flexible 

[mm

2

0.75

1.5 / 0.75

1.5 

1.0

4.0 / 0.75

1.5 

Stripped length 
(Solid/Stranded) 

[mm] 

10 / 10 

11 / 10 

Crimp 

Stranded 
Flexible 

[mm

2

0.75

2.5 / 0.75

2.5 

0.75

6.0 / 0.75

2.5

Max. Crimp 

[mm] 

7.7 / 7.7 

9.7 / 7.7 

Screw size 

M3.5 / M3.5 

M4 / M3.5 

Torque 

[N

m] 

0.8

1.0 / 0.8

1.0 

1.2

1.5 / 0.8

1.0 

5. Usage 

 

Thermal overload relay 

(1)

 

Push  the  reset  button  after  unpacking.  (Tripping  may  occur  by  the 

impact of transportation.) 

(2)

 

Turn the adjustment dial within the scale so that the full load current of 

the motor is at the  ▼  mark. (Fig.4) Do not use beyond the scale, or the 

expected performance cannot be obtained. 

(3)

 

By  pushing  the  trip  indicator  toward  the  arrow,  checking  of  control 

circuit wiring can be done. (Fig.4) 

(4)

 

When tripping occurs, the trip indicator disappears. (Fig.4) (But the trip 

indicator at automatic reset dose not disappears.)   

(5)

 

After  tripping  occurs,  pressing  the  reset  button  slightly  returns  the 

thermal  overload  relay  to  reset.  (If  the  thermal  overload  relay  is  not 

cooled sufficiently, it cannot be reset.) 

(6)

 

To  change  over  from  manual  reset  mode  to  automatic  reset  mode, 

keep the reset button pushed as shown in Fig.5. 

(7)

 

In the case of single phase, please change connection as follows. 

1.

 

Change  the  control  wiring  connected  with  “3-95”  to 

“5-95”. 

2.

 

Connect a main circuit as shown in the right figure. 

3.

 

Adjust  the  dial  to  10%  higher  than  its  rated  motor 

current. 

6. Maintenance and inspection 

6.1 Inspection before operation 

(1)

 

Check that all screws are tightened. 

(2)

 

Check that there is no foreign matter in the unit, such as wire chips 

or washers. 

(3)

 

Check  that  the  operating  circuit  voltage  is  within  the  allowable 

voltage fluctuation range of the coil voltage. The allowable voltage 

fluctuation range is 85 to 110% of the coil voltage.   

(4)

 

In AC operation, check that operation power supply is sinusoidal 

waveform (50Hz or 60Hz) without distortion or cave-in etc. 

6.2 Periodic inspection 

(1)

 

Perform  initial  inspection  early,  and  perform  subsequent 

inspections on a regular basis. 

(2)

 

Check  that  all  terminals  are  tightened  with  the  proper  torque 

periodically. 

(3)

 

The exchange for magnetic starter only in the case is not possible. 

(4)

 

Contacts and operating coil cannot be replaced at site. 

6.3 Others 

(1)

 

When  tripping  occurs,  open  the  cover  and  press  the  reset  button 

after removal of the failure cause (ex. overload). 

(2)

 

The  proper  torque  for  the  screws  with  the  cover  is 

“FJ-B09WP~B25WP:0.8~1.2[N・m], FJ-B32WP:2~2.5[N・m]”.

 

(3)

 

The  cover  of  FJ-B25WP  may  become  difficult  to  be  closed.  If  the 

load side wiring is moved a little more to the left, the cover can be 

closed easily.(Fig.6)

 

(4)

  The proper torque for the ground screw of FJ-B32WP is 2~2.5[

N・m

].

 

 
 

INSTRUCTION MANUAL

 

 

Mitsui Sumitomo Bank Ningyo-cho Bldg., 5-7, Nihonbashi 
Odemma-cho, Chuo-ku, Tokyo 103-0011, Japan 
Phone:+81-3-5847-8060 
Fax     :+81-3-5847-8182 
URL http://www.fujielectric.co.jp/fcs/eng/

 

INA-F0254-EC

This manual should be 
given to the person who 
actually uses the products 
and is responsible for their 
maintenance. 

TYPE 
  FJ-B09WP, FJ-B12WP, FJ-B18WP 
  FJ-B25WP, FJ-B32WP 

Fig.4

Fig.6

Fig.5

Fig.2 

190

 

M4×2

FJ-B09WP 

~FJ-B25WP 

250

 

M6×4

110 

FJ-B32WP 

Wiring 

Fig.1

A:Automatic 
M:Manual 

Reset 

button 

 

M

A

Operation display   
window 

Reset   
button   

Current setting
dial 

▼mark

 

Reset 

Trip 

Sequence check 

Trip indicator:white 

  (Displays it in the black for the
explanation) 

Fig.3

15° 

15° 

15° 

15° 