68
To check the sim card and
modem are working, enter
your mobile phone number
into
the ‘Test Telephone no’
box in international format as
shown opposite.
Click the
“
Send Test SMS
”
button.
This will send a text to your
phone confirming the phone number of the SIM and that calls can be made from the
modem. If you fail to receive a text message this could indicate a sim or modem fault
4.22
V
ERIFICATION OF THE CONFIGURATION
.
Ensure the program settings stored in IDT are transferred to the Sentinel; Click the
Setup Device button, as described earlier.
It is recommended to check the settings in Sentinel to check the configuration has been
correctly saved.
(i.e.
Click the “Read device” button and confirm all settings are correct
).
Check the status is also set to
“Record”
.
Check the PRV controller Start control button is green.
4.23
P
ROTECTION FROM
F
ROST
Where required, any tubing can be protected from frost with foam insulating pipe
covers. These can be supplied upon request at additional cost or sourced locally from a
hardware store.
To protect any required pressure transducers from frost, Sentinel 2 has the option of
being supplied with external transducers, rather than internal transducers. This
removes the possibility of the column of water within the pressure hoses connecting to
the internal transducers of the controller from freezing and potentially becoming
damaged, if left unprotected in harsh conditions.