4.2
Additional Settings (not included in installer)
All Settings, which are not editable are shown
in grey
. If you need to modify these values
contact FAUDI Aviation.
Network
IP Address
192.168.10.231
Change only if necessary
Subnet Mask
255.255.255.0
Internet Gateway
0.0.0.0
Modbus
Modbus RTU Slave Address
4
4
Analog Output
AO_3
N/A
optional
AO_4
N/A
optional
Relay Output
REL_1
Alarm, Inv
unchangeable
REL_2
Warning, Inv
unchangeable
REL_3
Ready
optional
REL_4
Off
optional
Digital Output
DO1
Flashlight
unchangeable
DO2
Off
optional
DO3
Off
optional
DO4
Off
optional
Water
Monitoring
Min. Flow for Monitoring
50 l/min
50 l/min
Min DP for Monitoring
0.05 bar
0.05 bar
Off delay Monitoring
300 sec
300 sec
Delay Begin of Monitoring
0 sec
0 sec
Minimum Fuel for Monitoring
0.0 l
0.0 l
AFGUARD Inlet
Level Water Slug
50 ppm
50 ppm
On Delay Water Slug
4 sec
4 sec
AFGUARD Outlet
Level Water Slug
50 ppm
50 ppm
On Delay Water Slug
4 sec
4 sec