22
Cons
no.
Note
Fact.
Adj.
Min.
Value
Max.
Value
Description
40
0
0
2
Analog Pressure gauge
0 = Digital Switch
1 = Analog Pressure gauge - Display units [BAR]
2 = Analog Pressure gauge - Display units [PSI]
41
0.50
0.10
5
Voltage Offset [V]
42
0.20
0.05
5
Voltage gain [V]
43
3.5
0.0
25.0
Pressure setpoint 0.0 - 25.0 [BAR]
Pressure level for Off - On
44
0.2
0.2
25.0
Pressure hysteresis 0.2 - 25.0 [BAR] *
Setpoint - 0.5 * hysteresis for Off
Se 0.5 * hysteresis for On
Default Settings 0.2
• 3.4 BAR = Off
• 3.6 BAR = On
Summary of Contents for FM4400H
Page 31: ...31...
Page 36: ...36 1 2 3 4 5 5 6 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 24 23 25 25 26 26 27 10 28...
Page 40: ...40 3 2 1 9 10 4 5 6 7 8...
Page 42: ...42 A1 B1 A1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27...
Page 48: ...48 1 3 4 2 A1 6 5 9 10 11 8 7 12...
Page 50: ...50 1 3 4 5 6 7 8 9 10 11 12 2...
Page 52: ...52 7 8 11 13 12 15 16 17 18 19 20 21 25 22 24 23 9 10 1 2 3 4 5 6 14...
Page 54: ...54 8 9 1 2 3 4 5 6 7 13 10 12 11 Solpanel s t 762080 stykliste 762080 1 2 4 5 3...
Page 56: ...56 1 2 3 4 5 6 A1 1 2 3 9 8 7 6 5 10 11 12 13 14 15 16 17 4...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60 1 2 3 4 5 6 7 9 10 4 11 2 1 12 13 14 15 16 17 16 17 18 19 20 8...
Page 62: ...62 B1 B2 B3 B4 4 2 3 10 11 6 5 7 8 9 1 12 13 1 14...
Page 68: ...68 B2 B3 B4 1 2 3 5 4 7 9 10 11 13 12 14 15 16 17 8 19 6 18 18...
Page 72: ...72...
Page 73: ...73...
Page 74: ...74 B2 B3 B4 1 2 3 4 5 6 7 8 12 11 10 9 13...
Page 78: ...78...
Page 80: ...80 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 21 20 22 23...
Page 82: ...82 3 3 4 3 3 2 Side 1 2 2 1 5 4 2 1 2...
Page 84: ...84 7 7 6 1 1 1 1 2 3 3 4 5 Side 2 2 2 6...
Page 86: ...86 1 2 2 1 3 4 5 6 7 8 9 10 9 4 3 2 1 11 9 12 4 13 11 14 15 16 17 18 19 19 20 21 5...
Page 88: ...88 15 B2 B3 1 2 3 4 5 6 6 7 8 9 10 11 12 13 14...
Page 90: ...90...
Page 92: ...92...
Page 94: ...94 1 2 B1 B2 16 17 18 19 20 21 3 3 4 5 6 7 8 9 10 11 12 13 14 15...