-15-
Voltage Input Range Setting Switch
(SW3)
4.1.3
Select the voltage input range by SW3 referring to the chart. Analog signals are converted to the digital data
according to the selected range of input voltage.
* If you use any channel in the current input mode, select the SDO Communication for the setting method
(SW3.1=OFF).
* Set SW3.1 before supply power to the module.
* SW3.2 is not used.
When using the DIP Switch for the setting method (SW3.1= ON), select voltage input range referring to the
chart.
[ Selecting Voltage Input Range ]
CH1/CH2
CH3/CH4
SW3.3
SW3.4
SW3.5
SW3.6
Input
Voltage
Range
-10 ~ 10V
OFF
OFF
OFF
OFF
-5 ~ 5V
OFF
ON
OFF
ON
-2.5 ~ 2.5V
ON
OFF
ON
OFF
0 ~ 10V
ON
ON
ON
ON
CH5/CH6
CH7/CH8
SW3.7
SW3.8
SW3.9
SW3.10
Input
Voltage
Range
-10 ~ 10V
OFF
OFF
OFF
OFF
-5 ~ 5V
OFF
ON
OFF
ON
-2.5 ~ 2.5V
ON
OFF
ON
OFF
0 ~ 10V
ON
ON
ON
ON
[ Selecting Input Setting Method ]
LSET
Description
SW3.1
Setting
Method
DIP Switch
ON
Setting voltage input range with DIP switches (SW3.3~SW3.10)
SDO Communication
OFF
Setting voltage/current input range through EtherCAT SDO communication