Air cooled water chillers and heat pumps
with radial fans
IDRA - RSC Series
Use, installation and maintenance manual
9
GB
IDRA RSC H 5 - 9m
Size
5
7
9m
Cooling capacity (1)
[kW]
5,2
6,5
8,4
Input power (1)
[kW]
1,9
2,5
2,8
Heating capacity (2)
[kW]
5,5
6,9
9,0
Compressors type
Recip. hermetic
Hermetic scroll
Compressors / circuits
1/1
1/1
1/1
Input power (each)
[kW]
1,9
2,5
2,8
Max. input power (each)
[kW]
4,2
3,4
4,58
Input current (each)
[A]
9,6
12,6
14,2
Max. input current (each)
[A]
22
17,8
24
Start-up current
[A]
55,0
91,0
85,0
Capacity steps
1
1
1
Evaporators / number Plate heat exchanger/1
Liquid fl ow
[m
3
/h]
0,9
1,1
1,4
Available static pressure
[kPa]
47,0
47,0
43,0
Storage tank volume
[l]
40
40
40
Fans Radial
Number 1
1
1
Air fl ow
[m
3
/h]
3500
3500
3500
Available static pressure
[Pa]
115
115
109
Max. input power (each)
[kW]
0,52
0,52
0,52
Max. input current (each)
[A]
3,80
3,80
3,80
Sound pressure level [dB(A)]
At 1 m from fan mouth
[dB(A)]
66
66
66
Dimensions and weights
Length
[mm]
1154
1154
1154
Width [mm]
679
679
679
Height
[mm]
900
900
900
Weight [kg]
158
162
167
Refrigerant charge
[kg]
2,2
2,5
2,9
(1) External air temp. 35°C, evap. water in/out temp. 12/7°C
(2) Water temp. 40/45°C, external air temp. 5°C
Size
5
7
9m
Total electrical data (230 V - 1 ph - 50 Hz)
Nominal input power
[kW]
2,4
3,0
3,3
Max. input power
[kW]
4,72
3,92
5,1
Nominal input current
[A]
13,4
16,4
18,0
Max. input current
[A]
25,8
21,6
27,8
Max. start-up current
[A]
58,8
94,8
88,8