Fantini Cosmi AP 20048 Instructions For Use Manual Download Page 1

CH193VMC

CENTRALISED CONTROL 

FOR VMC UNITS

Code:  AP 20048

AP 20050

              AP 20052

              AP 20054

              AP 20056

              AP 20058

INSTRUCTIONS FOR USE

FANTINI COSMI S.p.A.

Via dell’Osio, 6 20049 Caleppio di Settala, Milan – ITALY

Tel. +39 02 956821 | Fax +39 02 95307006 | [email protected]

www.fantinicosmi.it

Summary of Contents for AP 20048

Page 1: ...UNITS Code AP 20048 AP 20050 AP 20052 AP 20054 AP 20056 AP 20058 INSTRUCTIONS FOR USE FANTINI COSMI S p A Via dell Osio 6 20049 Caleppio di Settala Milan ITALY Tel 39 02 956821 Fax 39 02 95307006 info...

Page 2: ...el for the advanced control of ventilation systems through VMC Equipped with temperature relative humidity and VOC sensors it automatically controls ventilation and indoor air quality IAQ Note The CH1...

Page 3: ...i function touch icons 5 VMC ventilation status 6 Operating mode 7 Bar graph to display messages and daily programming Please note the function of the multi function keys varies depending on the situa...

Page 4: ...Communication mode ModBus RTU master Data formats 9600 bps 8 bits no parity 1 bit stop Maximum room temperature 45 C Storage temperature 10 C 60 C Rated pulse voltage 4000V Software Class A Insulation...

Page 5: ...ING TO THE PREVIOUS SETTINGS IS DISPLAYED 20 6 4 INTEGRATION ONLY AVAILABLE WITH THE INTEGRATION FUNCTION ACTIVE 21 6 5 AIR RETURN AIR TEMPERATURE PROBE INSIDE THE VMC 21 6 6 H2 EXHAUST AIR TEMPERATUR...

Page 6: ...iance with the requirements concerning the installation of electrical equipment ATTENTION Installation operations must be performed with the system s power disconnected CH193VMC must be installed on t...

Page 7: ...UNITS CH193VMC Place the rear body in the wall box Make the electrical connections refer to 2 ELECTRICAL CONNECTION and secure the rear body to the wall with the screws provided Hook the front of the...

Page 8: ...ical connections must be made by qualified personnel ATTENTION Electrical connection operations must be done with the system s power disconnected CH193VMC is connected directly to the Fantini Cosmi VM...

Page 9: ...here is an external demand for dehumidification and or heating cooling integration For all other machines a direct connection to the EXT IN input is sufficient It is necessary to set from Advanced Use...

Page 10: ...FIRM allows you to PROGRAM 3 1 DATE AND TIME SETTING Note by pressing always allows you to go back to the previous page Note To change the settings use the UP and DOWN arrows and the RIGHT and LEFT ar...

Page 11: ...f the VMC on 7 days and different for Summer Winter 2s 2 1 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF USER PROGR DATE AND TIME WINTER VMC PROFILE TEMP AUTO DISP VMC LOCK NO DATE AND TIME PROG PRESS x1...

Page 12: ...TCOMF When TEMP is selected AUTO is displayed then follow the procedure described in 3 and 4 Note Can be set from the Advanced Programming menu If the machine is designed to integrate heating and or...

Page 13: ...e only for WINTER OFF only for SUMMER In winter tE tC in summer tC tE Note Pressing ENTER to go to the next day Pressing COPY allows you to copy the temperature profile displayed to the following day...

Page 14: ...ALR C ALARM CLOSED ALR O ALARM OPEN INTEG INTEGRATION 2s 2 1 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF USER PROGR DATE AND TIME WINTER VMC PROFILE TEMP AUTO DISP VMC LOCK NO DATE AND TIME PROG PRESS...

Page 15: ...ows you to enter the set password and unlock the keyboard DISP INTEG the time schedule of the integration is displayed 18 0 1 DAY SEL TEMP PROG DISP OFF 2s 2 1 15 25 15 09 20 23 0 SEL TEMP PROG DISP O...

Page 16: ...me for an unlimited time until a new command is given AUTO WEEKLY PROGRAM The device manages time programme settings on a weekly profile Speeds V1 V2 V3 OFF can be set every half hour OFF SYSTEM OFF P...

Page 17: ...ELECTING THE OPERATING PROGRAM The ventilation programmes of the VMC are selected in cycles 2 1 2s 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF PRESS SEL 15 25...

Page 18: ...alue T MAN Manual Temperature between 5 and 35 C can be set Note adjustment does not depend on the room temperature read by the CH193VMC sensor but on the AIR probe inside the VMC see paragraph 6 5 AI...

Page 19: ...forttemperature temperature value between 5 and 35 C Note adjustment does not depend on the room temperature read by the CH193VMC sensor but on the AIR probe inside the VMC see paragraph 6 5 AIR RETUR...

Page 20: ...nd ventilation in MAN will be displayed VMC INT With integration off and ventilation in MAN will be displayed VMC V1 With ventilation in AUTO in both cases the set ventilation programme is displayed 1...

Page 21: ...MPERATURE PROBE INSIDE THE VMC VMC ONLY ON ENTER 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF AUTO 3 DAY 1 2 15 25 15 09 20 3 DAY ENTER 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF AUTO 3 DAY 1 2 15 25 15...

Page 22: ...R A ALARM OPEN INTEG INTEGRATION 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF AUTO 3 DAY 1 2 15 25 15 09 20 3 DAY ENTER H4 ENTER 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF AUTO 3 DAY 1 2 15 25 15 09 20...

Page 23: ...of ambient air quality detected by the sensor Quality of each notch very bad poor discreet good excellent 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF AUTO 3 DAY 1 2 15 25 15 09 20 3 DAY ENTER IAQ ENTE...

Page 24: ...ured the previous day TMIN minimum room temperature measured the previous day RESET Pressing DISP on the CURRENT MONTH PREVIOUS MONTH and CURRENT YEAR screens displays a graph with details on use show...

Page 25: ...ight with a duration that can be programmed between 5 and 30 seconds or always on 7 2 DISPLAY LIGHTING INTENSITY Allows you to modify the luminous intensity of the display at 10 levels 15 25 15 09 20...

Page 26: ...cally updates the time when it changes March and October default YES Allows the machine to be operated only in ventilation mode or with integration of heating from an external device 2s 2 1 DAY SAV YE...

Page 27: ...be set from 0 to 100 of the fan according to the logics defined in the following points The following functions can be selected by pressing PROG V1 V3 BOOST 1 15 25 15 09 20 23 0 SEL TEMP PROG DISP OF...

Page 28: ...DISP OFF AUTO 3 DAY 3s PRESS ENTER 2s 2 LIGHT ON 15S ENTER ADV PROGR VENTILAT PROG PRESS PROG 3 V1 50 ENTER PRESS UP TO PRESS UP TO Note BOOST can be set between the maximum of V3 and 100 7 5 3 BOOST...

Page 29: ...between 50 and 100 7 5 4 INT Can only be set if the Integration function is active 1 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF AUTO 3 DAY 3s INT 50 ENTER 2s 2 LIGHT ON 15S ENTER ADV PROGR VENTILAT P...

Page 30: ...um value of the set point operating range that can be set between 5 and 35 C T MIN T MAX 1 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF AUTO 3 DAY 3s 2s 2 LIGHT ON 15S ENTER ADV PROGR PRESS PROG 3 1 15...

Page 31: ...be managed Defines the maximum value of the set point operating range that can be set between 5 and 35 C T MIN T MAX DIFF 0 1 ENTER 1 TMAX 35 0 ENTER PRESS ENTER 15 25 15 09 20 23 0 SEL TEMP PROG DISP...

Page 32: ...eal height might not indicate the true temperature perceived Note the tA that can be set is between 5 0 and 7 0 C or OFF 2s 2 1 LIGHT ON 15S ENTER CORRECTION ENTER 26 0 PRESS ENTER ADV PROGR 15 25 15...

Page 33: ...NHEIT This allows you to choose the temperature display scale between Celsius and Fahrenheit degrees default CELSIUS LIGHT ON 15S ENTER CELSIUS ENTER 26 0 2s 2 1 PRESS ENTER CELSIUS FAHRENHEIT ADV PRO...

Page 34: ...he values detected by the relative humidity RH and room quality VOC sensors on the device If the relative humidity in the room exceeds the set point values the VMC automatically increases ventilation...

Page 35: ...100 to MAX MAX Off MID to 500 If the air quality in the room exceeds the set point values the VMC automatically increases ventilation to re establish optimum air quality 2s 2 1 LIGHT ON 15S ENTER SENS...

Page 36: ...R YES NO PRESS ENTER ITALIANO ENTER LIGHT ON 15S ENTER 2s 2 1 PRESS ENTER ITALIANO INGLESE RUSSO FRANCESE SPAGNOLO TEDESCO ADV PROGR ITALIANO ENGLISH FRANCAIS ESPANOL DEUTSCH PYCCK 15 25 15 09 20 23 0...

Page 37: ...rror SENS AIR AIR probe SENS H4 H4 probe BAD WATER blockage for harmful water SENS H2 H2 probe BAD H4 H4 unsuitable OT RESISTANCE high temp resistance MOTOR motor failure SW GRL SW GRL open BAD H2 H2...

Page 38: ...and 10 C can be set 7 15 EXT IN Allows you to set the input to be used on the system 2s 2 1 LIGHT ON 15S ENTER CHG 0 ENTER ADV PROGR 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF AUTO 3 DAY 3s D EXT T AM...

Page 39: ...stic signal when keys are pressed 2s 2 1 LIGHT ON 15S ENTER ALR SND NO ENTER ADV PROGR 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF AUTO 3 DAY 3s ALR SND YES ALR SND NO PRESS ENTER PRESS UP TO 2s 2 1 LI...

Page 40: ...ws the LED on the front of the CH193VMC panel to flash LIGHT ON 15S ENTER ADV PROGR CH193VMC V3 0 ENTER 2s 2 1 PRESS ENTER 15 25 15 09 20 23 0 SEL TEMP PROG DISP OFF AUTO 3 DAY 3s PRESS UP TO 2s 2 1 L...

Page 41: ...TERS This allows you to reset all the parameters except date and time to the factory settings LIGHT ON 15S ENTER ADV PROGR RESET NO ENTER 2s 2 1 PRESS ENTER 3 RESET YES ENTER PRESS ENTER RESET YES RES...

Page 42: ...icipating in the separate collection of products and batteries contributes to the correct disposal of these materials and therefore avoids possible negative consequences for the environment and human...

Page 43: ...43 CENTRALISED CONTROL FOR VMC UNITS CH193VMC...

Page 44: ...FANTINI COSMI S p A Via dell Osio 6 20049 Caleppio di Settala Milan ITALY Tel 39 02 956821 Fax 39 02 95307006 info fantinicosmi it www fantinicosmi it EN79973B 10 2021...

Reviews: