background image

PRODUCT ADVICE SHEET 

Fantech AVA series

 



VSD 

Remote electronic speed control in fan, blower, 

pump or applications where the torque varies with 

speed. Load independent speed control of universal 
& shaded pole motors. 



Energy efficient 3-wire PSC 

motor configuration. 2 

separate outputs for main / auxiliary windings. Can 

also be connected as simple 2-wire system. 



Power Control.

 Remote stepless electronic power 

control of resistive loads eg - lamps &  heaters. 



Multiple & dissimilar loads

 accommodated. 



EMI Filters built in. Ctick approved 

– no external 

filters required.  



Selectable input

 0–10 VDC or 2 – 20ma control 

signal with adjustable min / max levels.  



Factory calibrated 

for most fans or pumps. 



Easy

 

custom

 

calibration 

internal test source & 

simple range (span & offset) adjustments. 



Auto OFF at low signal levels

 

 <0.8V / 1.5ma 



Double isolation 

of control signal and mains 

circuitry via transformer and opto-isolation. 



Range of power ratings  

1200 VA - 7200 VA.  



Custom applications. Specific 

control parameters, 

interfaces, environmental probes. 



RoHS

 

compliant and Ctick approved. 



IP65 version available 

with removable base that 

can be separately drilled / mounted 

FEATURES 

Universal Power / VSD Controllers 

Part no. INST‐AVA VSD ADVICE    

 

 

 

 

 

August 2012 

 

 

 

 

 

SPECIFICATIONS    Fantech

    

Model AVA  Universal Power / VSD Controllers 

APPLICATIONS 

Speed control of most single phase PSC motors with mechanical loads such as fans, centrifugal pumps or 

those applications where the torque of the load varies with speed. Can also control shaded pole and 

universal motors with any type of mechanical load. Remote stepless power control of all general resistive and 
inductive loads such as lamp, heating elements or transformers. Multiple & dissimilar loads can be 

accommodated simply by connecting in parallel.  

TECHNICAL BASIS 

Phase angle control of  AC mains.  

B version 

– single output for small PSC motors connected as 2-wire, 

universal and shaded pole motors, lamps, heaters and transformers. 

D version 

– dual outputs for small, 

medium and large PSC motors and all other types of loads that require main & auxiliary control outputs.    

Standard proportional control via 0–10 V or 2-20ma DC control signal.  

RATINGS 

RMS continuous

 

Single phase 240 V AC (

+

10/

-

 20%) 50 Hz. Also available for 110V 60 Hz.      

AVA5.0 

– 1200 VA 5A     

AVA8.0 

– 2000 VA 8A     

AVA10.0 

– 2400 VA 10A.    

(other sizes also available) 

Main variable output  rated to full rated power and can be varied between ~20 and 100%.  
Auxiliary output is zero voltage solid state switched and can be rated up to 100% rated power. Total 

controlled plus auxiliary output power should not exceed 100% of maximum controller rated power.  

Environmental: up to 50

o

C in free air for AVA5.0 & AVA8.0 (no de-rating required). For AVA10.0 to 

AVA20.0 de-rate (max VA) 1.6% x “max VA rating” per 

o

C above 30

o

C. Max case temp all models 70 

o

C.  

PROTECTION 

Surge protection network incorporated on board for over voltage / noise spikes. Control circuit for remote 
control signal operates at 12 volts DC and is totally isolated from the supply mains / load power circuit by a 

double insulated fully encapsulated BS415 rated transformer and a 5000V opto coupler between control 

input & power output. Generous power design parameters – controller designed for PSC motor starting and 

reasonable short term overload conditions. On-board replaceable fuse in 

~L

  line.  External  DB  MCB 

overload / isolation protection recommended for motor load is usually adequate to protect  controller. 

CONTROL INPUTS 

0-10 volts terminals 

(+ve) & 

C

  with input resistance 1 Mohm.   2-20ma on terminals 

(+ve) & 

C

 with sink 

resistance = 500 ohm. An internal 10V DC source (max 50 ma) is provided between terminals 

A

(+) &

  C

 

which can be used for custom remote control applications, a remote or local potentiometer or testing.  

AUTO TURN-OFF

 

At low control levels, the controller is designed to shut down the main control and auxiliary outputs. Normal 

operation resumes at higher control levels. Auto turnoff occurs at < 0.8 VDC for voltage input, ~<5% for a  

potentiometer, < 1.5 ma for 2 - 20 ma.  

COMPLIANCE 

Fitted with internal Electromagnetic Interference suppression network, and complies with AS/NZS CISPR 
14.1:2003 when correctly installed.   ACA C-Tick lev 2  

N29529.  

      ROHS compliant. 

Summary of Contents for AVA Series

Page 1: ...d large PSC motors and all other types of loads that require main auxiliary control outputs Standard proportional control via 0 10 V or 2 20ma DC control signal RATINGS RMS continuous Single phase 240 V AC 10 20 50 Hz Also available for 110V 60 Hz AVA5 0 1200 VA 5A AVA8 0 2000 VA 8A AVA10 0 2400 VA 10A other sizes also available Main variable output rated to full rated power and can be varied betw...

Page 2: ...terminal block mounted inside enclosure end plate marked Mm Ma Mc L Lc Mm Controlled Output Motor main Up to 100 of total load NB controlled aux not to exceed 100 rated VA Ma Auxiliary Switched Output Motor aux for 3 wire control Up to 100 of total load Mc Common output Note Mc Lc are internally connected Connection of Mc optional if external common used L Mains input Lc Mains common input Scrn mi...

Page 3: ...g auxiliary loads ON OFF eg pilot lamps shutters contactor aux motor windings NB max total power of main and aux outputs must not exceed 100 of total controller rated power For PSC capacitor run motors there are 2 ways in which the motor may be wired to the controller The 3 wire configuration requires disconnection of one side of the capacitor from the main motor terminal route this as the 3rd wir...

Page 4: ...on DC voltmeter eg say 9V 5 Adjust MAX speed pot for desired maximum motor speed eg AC voltmeter across Mm and Mc eg say 220 235V AC 6 Decrease MAN pot setting to minimum control voltage on DC voltmeter eg say 1V 7 Adjust MIN speed pot for desired minimum motor speed eg AC voltmeter across Mm and Mc eg say 120V 8 Set SEL switch to AUTO Remove voltmeters 9 Replace end plate The controller is ready ...

Page 5: ...Part no INST AVA VSD ADVICE August 2012 Page ...

Reviews: