Rev.06
46/226
4.13. General settings.
General settings establish some parameters that are necessary for the relay to operate. These
settings are defined as general because they affect the entire relay, and as a result they are not
subject to a change of table.
Function
Description
Minimum
Maximum
Step
Unit
Default
General Settings
Equipment identifier
-
-
-
-
“free text”
Frequency
-
-
60/50
Hz
50
Serial number
-
-
-
-
0
Language
-
-
-
-
English
Active Settings Group
1
4
1
-
1
Phase Nominal Current
0.5
2.5
1, 5, 0.5 or 2.5
A
1
Neutral Nominal Current
50
800
1, 5, 0.5 or 0.1
A
1
Phase transformation ratio
1
3000
1
-
100
Neutral transformation ratio
1
3000
1
-
100
Local COM. Address
1
254
1
-
1
Remote address (1*)
1
254
1
-
3
Remote baudrate (1*)
4800
38400
-
bauds
19200
Remote Protocol
-
-
(2*)
-
IEC60870-5-
103
(1*) Remote communication parameters depend on model (protocol options:IEC60870-5-103, Modbus
RTU, IEC6185, DNP3.0 or IEC60870-5-104)
(2*) Modbus RTU or IEC60870-5-103 only in SILDxxxxxA(E,I)xxxx models.
1.
Equipment Identifier
. This is an ASCII text, for equipment identification. Normally protection
equipment is associated with a specific line or position, and this setting is used for this
identification. It is important that this field is filled in correctly, as the information regarding
events and oscillography are accompanied with this information.
2.
Frequency
. It is possible to select the frequency by general settings
3.
Serial number
is a read only setting
4.
Language
. The SIL equipment is capable of displaying their messages in four languages,
with English in all cases. Consult the list of models to find out which are available
5.
Active table
: see Settings Table.
6.
Nominal phase current
: it is possible to select the secondary phase nominal current.
Depending on model the options are: 5 A, 1A, 0.5 A or 2.5 A
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...