![FANOX SIL-A A Series User Manual Download Page 33](http://html1.mh-extra.com/html/fanox/sil-a-a-series/sil-a-a-series_user-manual_4588709033.webp)
Rev.04
33/112
Zone 1
: The machine is deenergized for a long time. Thermal image is 0%.
Zone 2
: We supply the machine with the nominal current. Thermal image evolutions so as to get the
value of the thermal balance corresponding to one time the nominal current Th = (I/It)
2
= 82%. The time
that it takes in getting the thermal balance depends on the adjusted heating constant.
Zone 3
: Once reached the thermal image corresponding to the application of one time the nominal
current, we apply 1.2 times the nominal current. Therma image will evolution so as to get the thermal
balance corresponding to 1.2 times the nominal current Th = (I/It)
2
= 119%. This would occur if we had
the permission of the thermal function disabled. If the permission is disabled, 49 protection function
performs when the thermal image reaches the value of 100%. Once tripped, current stops and thermal
image is getting cool based on the cooling constant.
Zone 4
: Before getting totally cool, nominal current is applied again and thermal balance is reached
once passed the time determined by the heating thermal constant.
Thermal image protection alarm bit is active if the thermal image measurement is over the adjusted
alarm level.
Thermal image protection trip bit is active when the measurement of the thermal image is over 100%
and it is reset when the measurement of the thermal image is under the adjusted alarm level.
4.10.2 Thermal overload with memory
Thermal image is stored in non-volatile RAM memory periodically every second. By this way, though the
relay loses the power supply, it will keep the thermal status of the machine.
4.10.3 Thermal overload measurement display. Reset.
Thermal image measurement is displayed on Measurement menu. Thermal image value reset is
possible in Commands menu (Reset TI). This command reset the value of the thermal image to the
value set in the alarm level.
Summary of Contents for SIL-A A Series
Page 8: ...www fanox com Rev 04 8 112 2 1 2 Case dimensions The dimensions are in mm...
Page 9: ...www fanox com Rev 04 9 112 2 1 3 Connection diagrams 2 1 3 1 Analog connections...
Page 12: ...www fanox com Rev 04 12 112 2 2 SILA with short circuitable current terminals 2 2 1 Front view...
Page 13: ...www fanox com Rev 04 13 112 2 2 2 Case dimensions The dimensions are in mm...
Page 14: ...www fanox com Rev 04 14 112 2 2 3 Connection diagrams 2 2 3 1 Analogic connections...
Page 22: ...www fanox com Rev 04 22 112 3 3 Functional diagram...
Page 61: ...www fanox com Rev 04 61 112...
Page 63: ...www fanox com Rev 04 63 112...
Page 64: ...www fanox com Rev 04 64 112...
Page 65: ...www fanox com Rev 04 65 112...
Page 111: ...www fanox com Rev 04 111 112 11 APPENDIX NOTES...