4.2 Function SOTF. Switch On To Fault
This protection function can be set by using the following parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
SOTF (*)
Switch On To Fault
Function Enable
-
-
No/Alarm/Trip/SHB Trip
-
No
Current Tap
0.010
30.000
0.001
xIn
5.000
Time Delay
0.000
300.000
0.001
s
0.050
Safe Time
0.000
300.000
0.001
s
2.000
(*) Optional depending on model
When the logic signal ‘
SOFT Start
’ is activated, it starts the
pickup of the function. This protection is
provided for high speed clearance of detected fault immediately after Manual Closure of Circuit Breaker
or any other conditions selectable through the logical signal.
The function is active during the time adjusted in Safe Time and this setting must be coordinated with
the Time delay in order to allow the correct behavior of the function.
The time delay is independent from the operating current flowing through the relay, so if the phase
current exceeds its predetermined value for an equal or greater amount of time than this preset value,
the protection function activates (trips) and does not reset itself until the average value of the phase
drops below the point of current pick-up. The function activates at 100% of the preset input and
deactivates at 95%. The reset is instantaneous.
The accuracy of the Time Delay is equal to the set time delay ±35ms or ±0.5% (whichever is greater).
Summary of Contents for SIL-A A Series
Page 8: ...www fanox com Rev 04 8 112 2 1 2 Case dimensions The dimensions are in mm...
Page 9: ...www fanox com Rev 04 9 112 2 1 3 Connection diagrams 2 1 3 1 Analog connections...
Page 12: ...www fanox com Rev 04 12 112 2 2 SILA with short circuitable current terminals 2 2 1 Front view...
Page 13: ...www fanox com Rev 04 13 112 2 2 2 Case dimensions The dimensions are in mm...
Page 14: ...www fanox com Rev 04 14 112 2 2 3 Connection diagrams 2 2 3 1 Analogic connections...
Page 22: ...www fanox com Rev 04 22 112 3 3 Functional diagram...
Page 61: ...www fanox com Rev 04 61 112...
Page 63: ...www fanox com Rev 04 63 112...
Page 64: ...www fanox com Rev 04 64 112...
Page 65: ...www fanox com Rev 04 65 112...
Page 111: ...www fanox com Rev 04 111 112 11 APPENDIX NOTES...