Rev.17
64/119
5.12. Test Menu
The SIA-F device has a test menu that can be used to check the operation of the signalling
components (LED indicators) and the outputs.
The following table shows the components that can be tested, along with their state depending on
whether they are activated or deactivated:
LED 1
Deactivated
LED 1 off
Activated
LED 1 green blinking
LED 2
Deactivated
LED 2 off
Activated
LED 2 red fixed
LED 3
Deactivated
LED 3 off
Activated
LED 3 red fixed
Trip Output
Deactivated
Trip Output deactivated
Activated
Trip Output activated
Output 2
Deactivated
Output 2 deactivated
Activated
Output 2 activated
Output 3
Deactivated
Output 3 deactivated
Activated
Output 3 activated
The following key sequence is used to gain access to the test menu: from the main menu, press
the keys “◄”, “▼”, and “►” in sequence and then press and hold the "OK" key until the "Test
menu" appears on the display. The test menu is accessed by pressing the "OK" key again, and the
“▲” and “▼” keys can be used to navigate through the different menu items. Each item can be
activated or deactivated by pressing "OK" on it (if the item is deactivated, it is activated by pressing
OK; if the item is activated, it
is deactivated by pressing “OK”). Press the “C” key to exit the test
menu.
To obtain more detailed information, the method for navigating the menus is explained graphically
in the keypad and display section.
5.13. Power supply
The SIA-F device is designed to be supplied from an auxiliary voltage of 24-220 Vdc/48-230 Vac
It can also be supplied from a USB cable which is connected through the serial port and goes
directly till PC permitting the power supply and the communication simultaneously.
Summary of Contents for SIA-F
Page 7: ...www fanox com Rev 17 7 119 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Frontal view...
Page 8: ...www fanox com Rev 17 8 119 2 2 Case dimensions The dimensions are in mm CUT OUT PATTERN...
Page 9: ...www fanox com Rev 17 9 119 2 3 Connection diagram 3 Phase CT and neutral CT Connection...
Page 10: ...www fanox com Rev 17 10 119 3 Phase CT and residual neutral Connection...
Page 34: ...www fanox com Rev 17 34 119...
Page 35: ...www fanox com Rev 17 35 119...
Page 36: ...www fanox com Rev 17 36 119...
Page 118: ...www fanox com Rev 17 118 119 NOTES...
Page 119: ...www fanox com Rev 17 119 119...