FANOX EMM-5 Instruction Manual Download Page 5

EMM-5 

instruction manual 

IM441-EU-F v0.4 

pag. 5  

SET GENERAL PARAMETER (

SET UP

)

Entry to menu: 

seT UP

Æ

seT Up 

RESET
SET DO1 
SET DO2 

SET HR_ 
DO_ OFF OFF 

SET CT

 

 

 

 

Increase

Set CT ratio 

 

 

 

 

 

 

from 

1

 to 

2000

 

 

 

Decrease

SET VT

 

 

 

 

Increase

Set VT ratio 

 

 

 

 

 

 

from 

0.1

to

400.0

 

 

 

Decrease

seT AV9 T

   

 

 

Increase

Set average time 

 

 

 

 

 

 

from 

1

 to 

30

 minutes   

 

Decrease

seT EN

 

 

 

 

TOT PAR

Set Energy visualization 

 

NORMAL

type 

seT 3pH

 

 

 

 

BALANC

Set connection 
Type  

 

UN_BAL

seT MDE

 

 

 

 

-3-

Set wiring connection 
type  

 

-4-

seT SYN MDE

 

 

 

L3

Set synchronism 

 

 

50

type  

 

60

seT PUL SE

Set pulse weight  

 

 

10.0

 kW-kVAr / pulse 

      (version 

with 

digital 

output)

01.0

 kW-kVAr / pulse 

0.10

 kW-kVAr / pulse 

0.01

 kW-kVAr / pulse 

seT TPL

  

 

 

 

Increase

from

100

to

500

 mS 

      in 

step 

by 

100 

mS 

 

  Decrease 

(version with digital output) 

seT ID ADR

  

 

 

Increase

Set address of network 

 

 

 

 

 

 

from 

001

 to 

127

 

  Decrease

(version with serial output)

seT SER BDR

Set baud rate    

19200 baud 

 

 

 

19.2

serial interface 

9600 baud

9.60

 (version

 with serial output

)

4800 baud

4.80

2400 baud

2.40

seT PAR

Set parameters of 

bit: 8data 1stop-no parity 

 

8.1  pAR NO

Comunication

bit: 8data 2stop-no parity 

  

8.2  paR NO

serial interface 

bit: 8data 1stop-even parity   

8.1  paR eVe

 

(version with serial output) 

bit: 8data 1stop-odd parity 

 

8.1  paR ODD

SET PAS

 

 

 

 

Increase

Set Password 

OFF

 - 

0002

 ÷ 

9999

Decrease

      Confirm 

and 

end 

of 

general 

settings 

www.fanox.com

[email protected]

Tel: 0034 94 471 14 09

Fax: 0034 94 471 05 92

Pag 5

Summary of Contents for EMM-5

Page 1: ...port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N 6 V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 6 V L L phase and three phase currents A kA A L1 A L2 A L3 6 A phase ...

Page 2: ...le voltage 400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral L2 L3 phase to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V phase to phase 175 290V phase neutral L3 N phase neutral power supply 110V 175 290V phase to phase 100 170V phase neutral The standard version allows to apply the instrument at all the thr...

Page 3: ... SINGLE PHASE LINE if the multimeters are used on single phase line the measure are referred at the L3 phase The others data displayed relatives at value of three phase system are not to consider I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM measure current inputs measure current inputs measure current inputs measure current inputs m...

Page 4: ...t energy counters If it s selected with the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x 1000 If it s selected with C key the display indicates the type of the energy displayed I...

Page 5: ... 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR Increase Set address of network from 001 to 127 Decrease version with serial output seT SER BDR Set baud rate 19200 baud 19 2 serial interface 9600 baud 9 60 version with serial output 4800 baud 4 80 2400 baud 2 40 seT PAR Set parameters of bi...

Page 6: ...rease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximum demand maxD Programming of the energy visualization type seT EN This setting allows to define the energy visualization type after the visualization of the temperature With TOT PAR will have the visualization of the partial and total energy counters With N...

Page 7: ...he enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page of Setup SETUP It s always possible to come back to measures visualization mode pressing at the same time the A and C keys PEAK VALUES AND ENERGY COUNTERS RESET RESET From the measures visualization mode pressing the A and C keys simultaneo...

Page 8: ... HI and ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the minimum threshold set ALR LO The activation of the alarm output will come after some seconds of delay set ALR DL In the REMOTE mode the output status will...

Page 9: ...OLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with low threshold value The B to increase and C to decrease keys are used to set the high and the low thresholds values The range depends by the parameter and it is linked to the CT and VT ratios Pressing A key to confirm The threshold set is ...

Page 10: ...and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO PAGE After the hour counter set the I O info page appears in F displays on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output DO2 The visualization of the sta...

Page 11: ...ton to select the parameter that can be displayed and indicated from E LED The voltage values are of the three phase system the frequency is of the L1 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in correspondence of the kWh and KVArh on the fro...

Page 12: ...xD avg I L1 max avg I L2 max avg I L3 max avg phase currents maximum of average phase currents max demand max maxD avg 6 W max avg 6 VAr max avg 6 VA max avg three phase power maximum of average three phase powers maximum demand max maxD avg I L1 avg I L2 avg I L3 avg phase currents average phase currents max maxD avg 6 W avg 6 Var avg 6 VA avg three phase power average three phase powers max maxD...

Page 13: ...32 485 converter between the RS232 PC s outlet and the instrument s it s necessary to insert a line termination resistance Rt 100 120 ohm between the twisted pair of cables placing it between the converter and the end of the network last instrument connected Use always twisted cables with minimum section of 0 36mm2 22AWG and lower capacity of 60 pF m i e BELDEN cable type EIA RS485 Ref 3105A Shiel...

Page 14: ...EMM 5 instruction manual IM441 EU F v0 4 pag 14 DIMENSIONS 92 92 R3 96 96 90 96 56 9 20 cut panel www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 14 ...

Page 15: ...single phase insertion in MT with external TV and transforming rate programmable from 0 1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA Insulation 3kV for 60 second Pulse Function Weight programmable 0 ...

Page 16: ...M425 UE F v2 2 pag 16 Parque Tecnológico de Bizkaia Edif 604 48160 DERIO BIZKAIA ESPAÑA Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 E mail fanox fanox com Web www fanox com www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 16 ...

Reviews: