FANOX EMM-5 Instruction Manual Download Page 15

EMM-5 

instruction manual 

IM441-EU-F v0.4 

pag. 15  

TECHNICAL FEATURES 

MEASURES, PRECISIONS 
voltage 

true RMS of the phase voltages and the phase to phase voltages and values of three phase system 
range of total measure: 20÷500V trms phase-phase - 290V rms phase-neutral dependent by the auxiliary 
power supply 
visualization (0,02÷50,0kV)  -  measure precision: ±0,5% ±1 digit– management maximum values 

current 

true RMS of the phase currents and of the value of three phase system 
range of measure: 0,02÷5A trms   -  measure precision: ±0,5% ±1 digit 
visualization 0,02÷9990A – management average and maximum values 

frequency 

frequency of the L3 phase –range of measure: 30÷500Hz 
precision: ±0,5% ±1 digit 

powers 

phase and three phase system reactive and active power 
range of measure: 0,001÷9990kW - 0,001÷9990kVAr - 0,001÷9990kVA 
precision: ±1% ±1 digit  -  management average and maximum value 

power factor 

phase and three phase power factor 
range of measure: -0,1÷0,1 / precision: ±1% ±1 digit - management average and maximum value 

energy measure 

three phase system active, reactive and apparent energy 
range of measure:  0÷99999999,9 kWh / kVArh 

class 2 ( IEC 1036) 

precision: ±1% 

hours counter 

precision: ±1%; resolution 1/10 of hour 

AUXILIARY POWER SUPPLY, INPUTS 
auxiliary power 
supply 

standard 380-415V ±15%  -  optional 100-125 / 220-240V ±15% 
frequency 50-60Hz - consumption 3VA 
voltage from the voltage measure input 

voltage inputs 

from 20 to 500V phase-phase (dependent from auxiliary power supply); permanent ov20% -  input 
impedance: 1 M

:

insertion on three phase line with 3 wires, 4 wires and single phase 
insertion in MT with external TV and transforming rate programmable from 0.1 to 400.0 

current inputs 

from 0,02 to 5A; permanent overload 30% - from external TA with secondary 5A, 
primary programmable from 5 to 10000A  -  auto-consumption <0,5VA 

 INPUTS / OUTPUTS 
digital outputs 

Two outputs with common, optomos 12÷230Vac/dc, max 150mA,
Insulation: 3kV for 60 second 
Pulse Function: 
Weight programmable 0,01-0,1-1-10 kWh/pulse 
Pulse duration 100-200-300 400 500 milliseconds selectable 
DO1: active energy pulse output 
DO2: reactive energy pulse output 

serial output 

One optional output RS485, baud rate selectable, MODBUS-RTU protocol 
Insulation: 3kV for 60 second 

GENERALS
display, operators  4 displays with red LED 10mm everyone of 3 digit by 7 segments 

3 push-button for selecting measure and programming 

mechanic 

protection degree: IP52 frontal  -  IP20 enclosure and terminals  -  weight: about 0,5 kg 
connections with screw terminals for cable 2,5 mm

2

enclosure thermoplastic self-extinguishing  -  flush mounting DIN 96x96mm, depth 56mm 

environmental 

working temperature: -10÷60°C;  humidity <90% 
storing temperature: -25÷70°C 
insulation test: 3 kV for 1 minute 

standards 

CEI EN 50081-2; CEI EN 50082-1; 
CEI EN 61010-1 

NOTE  

At reason of the evolution of standards and products, the company reserves to modify in every time  the features of the product described in this 
document, that it’s necessary to verify preventively. 
The liability of the producer for damage caused by defect of the product ”can be reduced or deleted (…) when the damage is caused joint by a defect of 
product or for blame of the damaged or a person of which the damaged is responsible” (Article 8, 85/374/CEE).

www.fanox.com

[email protected]

Tel: 0034 94 471 14 09

Fax: 0034 94 471 05 92

Pag 15

Summary of Contents for EMM-5

Page 1: ...port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N 6 V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 6 V L L phase and three phase currents A kA A L1 A L2 A L3 6 A phase ...

Page 2: ...le voltage 400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral L2 L3 phase to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V phase to phase 175 290V phase neutral L3 N phase neutral power supply 110V 175 290V phase to phase 100 170V phase neutral The standard version allows to apply the instrument at all the thr...

Page 3: ... SINGLE PHASE LINE if the multimeters are used on single phase line the measure are referred at the L3 phase The others data displayed relatives at value of three phase system are not to consider I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM measure current inputs measure current inputs measure current inputs measure current inputs m...

Page 4: ...t energy counters If it s selected with the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x 1000 If it s selected with C key the display indicates the type of the energy displayed I...

Page 5: ... 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR Increase Set address of network from 001 to 127 Decrease version with serial output seT SER BDR Set baud rate 19200 baud 19 2 serial interface 9600 baud 9 60 version with serial output 4800 baud 4 80 2400 baud 2 40 seT PAR Set parameters of bi...

Page 6: ...rease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximum demand maxD Programming of the energy visualization type seT EN This setting allows to define the energy visualization type after the visualization of the temperature With TOT PAR will have the visualization of the partial and total energy counters With N...

Page 7: ...he enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page of Setup SETUP It s always possible to come back to measures visualization mode pressing at the same time the A and C keys PEAK VALUES AND ENERGY COUNTERS RESET RESET From the measures visualization mode pressing the A and C keys simultaneo...

Page 8: ... HI and ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the minimum threshold set ALR LO The activation of the alarm output will come after some seconds of delay set ALR DL In the REMOTE mode the output status will...

Page 9: ...OLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with low threshold value The B to increase and C to decrease keys are used to set the high and the low thresholds values The range depends by the parameter and it is linked to the CT and VT ratios Pressing A key to confirm The threshold set is ...

Page 10: ...and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO PAGE After the hour counter set the I O info page appears in F displays on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output DO2 The visualization of the sta...

Page 11: ...ton to select the parameter that can be displayed and indicated from E LED The voltage values are of the three phase system the frequency is of the L1 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in correspondence of the kWh and KVArh on the fro...

Page 12: ...xD avg I L1 max avg I L2 max avg I L3 max avg phase currents maximum of average phase currents max demand max maxD avg 6 W max avg 6 VAr max avg 6 VA max avg three phase power maximum of average three phase powers maximum demand max maxD avg I L1 avg I L2 avg I L3 avg phase currents average phase currents max maxD avg 6 W avg 6 Var avg 6 VA avg three phase power average three phase powers max maxD...

Page 13: ...32 485 converter between the RS232 PC s outlet and the instrument s it s necessary to insert a line termination resistance Rt 100 120 ohm between the twisted pair of cables placing it between the converter and the end of the network last instrument connected Use always twisted cables with minimum section of 0 36mm2 22AWG and lower capacity of 60 pF m i e BELDEN cable type EIA RS485 Ref 3105A Shiel...

Page 14: ...EMM 5 instruction manual IM441 EU F v0 4 pag 14 DIMENSIONS 92 92 R3 96 96 90 96 56 9 20 cut panel www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 14 ...

Page 15: ...single phase insertion in MT with external TV and transforming rate programmable from 0 1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA Insulation 3kV for 60 second Pulse Function Weight programmable 0 ...

Page 16: ...M425 UE F v2 2 pag 16 Parque Tecnológico de Bizkaia Edif 604 48160 DERIO BIZKAIA ESPAÑA Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 E mail fanox fanox com Web www fanox com www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 16 ...

Reviews: