background image

                                                                                                                                                                                                                                               

 

Page:10/18                                                                                                                                               

 

10 

Figure

 5                                                 

Figure

 6

 

Important Notice:

 

The length of the exhaust hose shall be 280~1,500mm, and this length is based on the specifications of the 
air conditioning. Do not use extension tubes or replace it with other different hoses, or this may cause a 
malfunction. Exhaust host must be not blocked; otherwise it may cause overheating. 

 

VI.Drainage Instructions 

This machine has two drainage methods: manual drainage and continuous drainage. 

1

Manual drainage: 

1)  When the machine stops after the water is full, turn off the machine power and unplug the power 

plug. 
Notes

Please move the machine carefully, so as not to spill the water in the water pan at the 

bottom of the body.   

2)  Place the water container below the side water outlet behind the body. 

3)  Unscrew the drainage cover and unplug the water plug, the water will automatically flow into the 

water container

.

 

 

 

 

 

 

 

 

 

Notes

1

Keep the drainage cover and the water plug properly.   

2

During drainage, the body can be tilted slightly backwards. 

3

If the water container cannot hold all the water, before the water container is full, stuff the water outlet   

with the water plug as soon as possible to prevent water from flowing to the floor or the carpet. 

4

When the water is discharged, stuff the water plug, and tighten the drainage cover 

 

2

Continuous drainage (Optional) (only applicable to dehumidifying mode), as shown in figure:   

1) Unscrew the drainage cover, and unplug the water plug. 
2) Set the drainage pipe into the water outlet. 
3) Connect the drainage pipe to the bucket

 

 

 

 

 

 

 

 

Summary of Contents for PAH-9016

Page 1: ...Page 1 18 1 LOCAL AIR CONDITIONER PAH 9016 Instructions Manual Read and save these instructions ...

Page 2: ...n 6 V Installation and adjustment 7 VI Drainage Instructions 9 VII Maintenance 10 VIII Out of season save 10 IX Troubleshooting 11 X Addendum 11 Please read these instructions before use and repair The drawings provided in this manual may not be the same as the physical objects Please refer to the physical objects ...

Page 3: ...anufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants 12 All working procedure that affects safety means shall only be carried by competent persons Notes The air conditioning is only suitable for indoor use and is not suitable for other applications Follow local ...

Page 4: ...dren shall not play with the appliance Cleaning and maintenance shall not be made by children without supervision If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The appliance shall be installed in accordance with national wiring regulations Do not operate your air conditioner in a wet room such as a ...

Page 5: ...ability Timing switch function Protection function of automatically restarting the compressor after three minutes a variety of other protection functions Max operation temperature for the air conditioner Cooling 35 24 heating 20 12 Temperature operation range 7 35 2 Components ...

Page 6: ... change the setting temperature or setting time operate as follows While setting temperature press up key or down key to select the required temperature not available in fan or dehumidifying mode While setting time press up key or down key to select the required time 6 Wind Speed Selection Key In cooling Heating and fan mode press the key to select high low wind speed operation But limited by anti...

Page 7: ...ress the key to switch between cooling dehumidifying fan heating mode 5 Up press the key to increase temperature and timing set value 6 Fan press the key to select high low wind speed 7 Sleep Mode Press the key to turn on the sleep mode IV Protection function 3 1 Frost Protection Function In cooling dehumidifying or economic power saving mode if the temperature of the exhaust pipe is too low the m...

Page 8: ... be placed on a flat surface Do not install and use the air conditioning in the bathroom or other humid environments 1 1 Install the heat pipe assembly as shown in Fig 1 Figure 1 1 take out the outer connector assembly and the exhaust pipe assembly and remove the plastic bags 2 insert the heat pipe assembly the end of the exhaust joint into the back panel vent slot push to the left and complete th...

Page 9: ... and fittings before the window and the distance between the body and walls or other objects shall be least 50 cm as shown in Fig 4 Figure4 2 Elongate the exhaust pipe and snap the flat end of the exhaust pipe joints into the hole of the window sealing plate assembly as shown in Fig 5 and Fig 6 Notes 1 The flat end of the exhaust pipe joints must be snapped into place 2 The pipe cannot be distorte...

Page 10: ...at the bottom of the body 2 Place the water container below the side water outlet behind the body 3 Unscrew the drainage cover and unplug the water plug the water will automatically flow into the water container Notes 1 Keep the drainage cover and the water plug properly 2 During drainage the body can be tilted slightly backwards 3 If the water container cannot hold all the water before the water ...

Page 11: ...ater with neutral detergent about 40 104 and dry it in the shade after rinsing clean VIII Unit Storage i Unscrew the drainage cover unplug the water plug and discharge the water in the water pan into other water containers or directly tilt the body to discharge the water into other containers ii Turn on the machine adjust it to low wind ventilation mode and maintain this state until the drainage p...

Page 12: ...pment shall be available to hand Have a dry powder or CO2 fire extinguisher adjacent to the charging area 6 No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion All possible i...

Page 13: ...m the equipment being worked upon prior to any removal of sealed covers etc If it isabsolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation 2 Particular attention shall be paid to the following to ensure that by working on electrical c...

Page 14: ...ated by means of shut off valves in a part of the system remote from the leak Oxygen free nitrogen OFN shall then be purged through the system both before and during the brazing process 7 Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important that best practice is followed since flamma...

Page 15: ...he appropriate standards d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so that refrigerant can be removed from various parts of the system f Make sure that cylinder is situated on the scales before recovery takes place g Start the recovery machine and operate in accordance with manufacturer s instructions h Do not overfill cylinders No more than 80 volume...

Page 16: ...make certain that flammable refrigerant does not remain within the lubricant The evacuation process shall be carried out prior to returning the compressor to the suppliers Only electric heating to the compressor body shall be employed to accelerate this process When oil is drained from a system it shall be carried out safely Fuse parameters of the machine Type FSD or 50F Voltage 250V Current 3 15 ...

Page 17: ...re other sources of heat Close doors and windows and add new air conditioning The filter screen is dirty Clean or replace the filter screen The air inlet or outlet is blocked Clear obstructions Big Noise The air conditioning is not placed on a flat surface Put the air conditioning on a flat and hard place to reduce noise compressor does not work Overheat protection starts Wait for 3 minutes until ...

Page 18: ...llection recycling centre In the European Union there are separate collection systems for used electrical and electronic products Please help us to conserve the environment we live in DECLARATION OF CONFORMITY Herewith Amiridis Savvidis S A states that this product complies with the requirements of below directives EMC Directive 14 30 EU Low Voltage Directive 14 35 EU ErP Directive 09 125 EC CE Ma...

Reviews: