LE-03

Electric energy meter,

3-phase

The LE-03 is a static (electronic) calibrated electricity meter of 

three-phase alternating current in a direct system. 

A special electronic system under the influence of flowing cu-

rrent and applied voltage in each phase generates pulses pro-

portional to the energy drawn in the respective phase. Energy 

consumption in the phase is indicated by a flashing of corre-

sponding LED (L1, L2, L3). The sum of the three phase pulses is 

indicated by a flashing LED and converted into energy absorbed 

throughout the three-phase system. Its value is displayed by the 

mechanical drum abacus.

The last, red number on the drum abacus indicates row 1/10 

kWh (100 Wh).

Purpose

Functioning

F&F Filipowski sp. j.

Konstantynowska 79/81, 95-200 Pabianice, POLAND

phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71

www.fif.com.pl; e-mail: [email protected]

Do not dispose of this device in the trash along with other waste! 

According to the Law on Waste, electro coming from households free of charge and can 

give any amount to up to that end point of collec� on, as well as to store the occasion of 

the purchase of new equipment (in accordance with the principle of old-for-new, regard-

less of brand). Electro thrown in the trash or abandoned in nature, pose a threat to the 

environment and human health.

Summary of Contents for LE-03

Page 1: ...the three phase system Its value is displayed by the mechanical drum abacus The last red number on the drum abacus indicates row 1 10 kWh 100 Wh Purpose Functioning F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48 42 227 09 71 www fif com pl e mail biuro fif com pl Donotdisposeofthisdeviceinthetrashalongwithotherwaste According to the Law on Waste elec...

Page 2: ... reading pulses generated by the counter For proper operation of the indicator is not required to connect additional devices The meter is marked with individual serial number allowing its unambiguous identification The marking is laser engraved and cannot be removed Measured value Pulse output Meter number ...

Page 3: ... 3 The meter has sealable input and output terminal covers to pre vent any attempts to bypass the meter Sealing ...

Page 4: ...ver remove the screws and remove the front shield meter terminals 4 Connect power to terminals 1 L1 3 L2 5 L3 5 N wire connect to terminal 7 6 Additional pulse receiver connected optional to terminals 9 and 8 Additional pulse receiver is not required 7 Put the meter terminals covers Front description Mounting ...

Page 5: ... 5 1 power input L1IN 6 power output L3OUT 2 power output L1OUT 7 N wire neutral 3 power input L2IN 8 pulse output 4 power output L2OUT 9 pulse output 5 power input L3IN Wiring diagram ...

Page 6: ...ial own power consumption 10 VA 2 W indication range 0 999999 9 kWh constant 800 pulses kWh current consumption signalling L1 L2 L3 phases 3 red LED read out signalling red LED pulse output type open collector maximum voltage 27 V DC maximum current 27 mA pulse time 35 80 ms working temperature 20 55 C terminal 25 mm screw terminals dimensions 7 modules 122 mm mounting on TH 35 rail ingress protec...

Page 7: ... j declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE Declaration of Conformity along with the references to the standards in relation to which conformity is declared can be found www fif com pl on the product subpage Dimensions Warranty CE declaration ...

Page 8: ...sure that all cables are connected correctly It is essential to observe the operating conditions of the meter supply voltage humidity temperature To avoid electric shock or damage to the meter turn off the power supply whenever the connection is changed Do not make any changes to the unit yourself Doing so can result in damage to or improper operation of the device which in turn can pose a threat ...