G
11
g
Each connected IVM-Touch input / output has a unique address for the I/O-network. Set the I/O-addresses in the
climate controller as follows:
I/O-network input / output
IVM-Touch address . sequence number
Analog input 1 (temperature)
“IVM-Touch address” . 1
Analog input 2 (e.g. RH)
“IVM-Touch address” . 2
Relay output 1
“IVM-Touch address” . 1
Relay output 2
“IVM-Touch address” . 2
RPM feedback-measurement /
Digital input 1
“IVM-Touch address” . 1
Digital input 2
“IVM-Touch address” . 1
Control analog output 1 or triac
“IVM-Touch address” . 1
Analog output 1
“IVM-Touch address” . 2
Analog output 2
“IVM-Touch address” . 3
Triac 1
“IVM-Touch address” . 4
Triac 2
“IVM-Touch address” . 5
After an address has been changed, the network module should always be restarted (power off-on).
Set the dipswitch settings on Print ICM board
There are two options for controlling the speed of the fans. Either the speed is based on the temperature sensor
in the IVM-Touch or it is based on an analog setpoint which is set in the climate controller. Set the red and white
dipswitches on the ICM board to define the prefered option.
Analog in 1
Analog in 2
Fan control by:
Dip 1
Dip 2
Dip 3
Dip 4
Temperature
On
Off
On
Off
Setpoint
Off
On
Off
On