6.12 Automatic test alarm/routine call
This function calls a test alarm/routine call receiver to verify the connection between the Fält-
com ECII® Flex and the alarm receiver. Automatic test alarm/routine call shall only be pro-
grammed if the lift phone is connected to an alarm central, the alarm central can verify that
the incoming test alarms/routine calls are correct. A test alarm/routine call is silent; no tones
are heard in the lift.
When the test alarm/routine call function is activated the first test alarm/routine call is sent 5
minutes after exiting programming mode and the following test alarm/routine call is sent 10
hours after the first. The third and following test alarm/routine call are sent every N x 24 hours
where N is the test alarm/routine call interval in days. Note that the automatic test counter is
reset every time an automatic test related parameter is changed and when the power is dis-
connected from the lift phone. If the lift phone has been out of power and the power returns it
will send the next test alarm/routine call after 10 hours.
If a test alarm/routine call fails the next attempt is made after 10 minutes. In total 10 attempts
are made. If a test alarm/routine call is received for instance in the third attempt the next test
alarm/routine call will be sent N x 24 hours after the last attempt. This means that the lift
phone automatically distributes the test alarms/routine calls to a time when the telephone line
of the alarm receiver is normally available.
It is also possible to make the Fältcom ECII® Flex call out an additional test alarm/routine call
after each main alarm. To do this, use alternative 1b instead of 1a.
Activation of test alarm/routine call
1 a. Select the required test interval: 1 to 30 days. (Use a number between 1 and 30.)
From keypad:
<Days (1 – 30)>
From phone:
080
< 1 – 30 > #
If the test alarm/routine call should go to the same receiver as AR1 and use the same
code; no more programming is needed. If it will go to an individual number, continue
to paragraph 2.
Activation of test alarm/routine call after main alarm
1 b.
Select the required test interval: 1 to 30 days. (Use a number between 1 and 30.)
From keypad:
<Days (1 – 30)>
From phone:
082
< 1 – 30 > #
If the test alarm/routine call should go to the same receiver as AR1 and use the same
code; no more programming is needed. If it will go to an individual number, continue
to paragraph 2.