Synergy Series Soft Start User Manual
MAN-SGY-017. Version 01. 27/06/2016
43
37.2 Parameter Summary for Touchscreen Setup
–
“I/O” Category
(continued)
–
Group
Parameter
Units Range
Read /
Write
Modbus
Default
Setting
User
Setting
Dec Hex
Ca
te
go
ry
–
I/
O
Analog
Outputs
Analog Output Type
toggle 0–10V / 4–20mA
R/W
8960 2300 0–10V
Select Function
–
Off
Current
Measured
Overload
Overload SCR
P-Total
R/W
9024
2340
OFF
Scaling Level
–
0 to 16,384
R/W
9088 2380 0
PTC Motor Thermistor Trip
toggle
OFF / ON
R/W
53794
D222
OFF
3.7.3 Summary
–
Parameters for Touchscreen Setup
–
“Monitor” Category
Ca
te
go
ry
–
M
on
it
or
Group
Parameter
Units Range
Read /
Write
Modbus
Default
Setting
User
Setting
Dec
Hex
Monitoring
Line Frequency
Hz
45 to 65
Read
32000 7D00 n/a
–
Phase Rotation
–
L1-L2-L3 or L1-L3-L2
Read
32064 7D40 L1-L2-L3 –
I1
A
0 to 10,000
Read
33536 8300 0
–
I2
A
0 to 10,000
Read
33538 8302 0
–
I3
A
0 to 10,000
Read
33540 8304 0
–
Current I rms
A
0 to 10,000
Read
32896 8080 0
–
V rms (Approx)
V
0 to 500
Read
32960 80C0 0
–
Real Power Factor
–
0 to 1
Read
33024 8100 0
–
True Power P
kW
0 to 10,000
Read
34688 8780 0
–
Apparent Power S
kVA
0 to 10,000
Read
34816 8800 0
–
Reactive Power Q
kVAR
0 to 10,000
Read
34944 8880 0
–
iERS Saving Level
%
0 to 100
Read
35008 88C0 0
–
Delay Angle
degree 0° to 55°
Read
22400 5780 0
–
Backstop
degree 0° to 55°
Read
23040 5A00 0
–
Delay Max
degree 0° to 55°
Read
22464 57C0 0
–
Pres PF Degrees
degree 0° to 90°
Read
21824 5540 0
–
Ref PF Degrees
degree 0° to 90°
Read
21760 5500 0
–
Start Saving Level
%
50% to 80% of mtr FLA Read
21320 5348 80%
–
Last Peak (Start) Current
A
0 to 10,000
Read
38400 9600 0
–
HeatSink Temp
°C
-20°C to 80°C
Read
36544 8EC0 ambient –
Motor Thermistor
–
0 to 1024
Read
10432 28C0 0
–
Overload
%
0 to 100
Read
33408 8280 0
–
3. Configuration and Parameters (continued)
Summary of Contents for synergy
Page 1: ...Innovation in soft start technology synergytm USER MANUAL MAN SGY 017 Version 01...
Page 20: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 25 07 2016 20 Blank Page...
Page 27: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 25 07 2016 27 Blank Page...
Page 33: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 33 Blank Page...
Page 84: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 84 Blank Page...
Page 100: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 100 Blank Page...
Page 106: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 106 Blank Page...
Page 112: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 112 Blank Page...
Page 129: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 129 Blank Page...
Page 197: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 197 Blank Page...
Page 204: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 204 Blank Page...
Page 231: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 231 Notes...
Page 232: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 232 Notes...
Page 233: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 233...