page 11 FD7A49-F O81112
Operational Voltage (Ue)
230-460 VAC rms 3-Phase (-15% +10%)
Rated Frequency
50 - 60Hz +/- 2Hz
Form Designation
Form 1
Index Rating
Standard AC53b: 3-5: 355 (10 Starts/Hr)
Control Supply
24V DC approx 4VA supplied externally to terminals X1-X2.
Power supply kit (12VA) available as part No. AMISC0005.
Start/Soft Stop Control
24V DC/110V AC galvanically isolated terminals A1-A2
Auxiliary Circuits
(relays)
Run - 13/14, Ready - 23/24. 230VAC 3A, AC11.
Indication
Multi function LED on front panel
Start Time
1 to 30 seconds.
Stop Times
0 to 30 seconds
Start Duty
3 x FLC for 5 seconds at standard rating
Starts / Hour
10 starts per hour or 5 5 soft stops per hour
Power Terminals
Input - 1/L1, 3/L2 & 5/L3
output - 2/T1, 4/T2 6/T3.
Up to 55kW (97Amp)
Wire clamp terminals (unit is IP20)
75kW to 110kW (132Amp to 197Amp)
External busbars (unit is IP00)
ModelName
400/460V
Range
Class 5 @40°C
3 x FLC for 5seconds
10 starts per Hr
Ferraz Fuse for
Type 2 coordination
short circuit
protection
Ie
(Arms)
Motor kW
at 400V
22A
11kW
6,9 URD 00 D08L 050
6,9 URD 00 D08L 100
6,9 URD 00 D08L 125
6,9 URD 31 D08L 200
6,9 URD 31 D08L 250
6,9 URD 31 D08L 400
29A
15kW
41A
22kW
55A
30kW
66A
80A
97A
132A
160A
195A
37kW
45kW
55kW
75kW
90kW
110kW
DFE-02
DFE-04
DFE-06
DFE-08
DFE-12
DFE-14
DFE-16
DFE-22
DFE-24
DFE-26
Earth Terminal
External stud
Up to 30kW/55Amp M6
37kW/66A to110kW/195Amp M8