Electrical Installation
FD8413 issue03_F
2.10.5
Overcurrent Trip Graph
0.01
0.1
1
10
100
1000
1
2
3
4
5
6
7
8
9 10
Fault current ( Motor Current x N )
Seconds
to trip
Overload start point
Delay = 80
Delay = 30
Delay = 10
P35 (or P94)
Default
Delay = 140
‡
(adjustable by P34 (or P93) ‡; default setting: 110%)
‡
Parameter selected through either the primary or secondary group of value parameters
'Current limit', 'Overload level' and 'Overload delay' settings may be adjusted to limit overload
currents in accordance with the trip curves shown here.
For motors with FLC's
lower
than the rated current of the QFE the Overload level' may be
adjusted using the following formula:
Overload level = Motor FLC x 1.1 (A)
Notes:
1
The overload monitors one of the phases only and the 'Current Limit' level
is only active during motor starting.
2
It is recommended that the control supply is maintained between starts to
ensure the integrity of the overload, which will reset on it's removal
Summary of Contents for QFE Series
Page 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Page 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Page 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Page 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Page 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Page 73: ...QFE page 3 25 Applications FD841405_F...
Page 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Page 181: ...Modbus page 6 4 5MC FD510007...