Electrical Installation
QFE
page 2-18
FD8413 issue03_F
2.7.3
Control Outputs - All models
Identification
Description
12, 14, 11
Programmable Output, Relay K1.
A Bit = 1 on the parameter/bit selected by P57 makes Relay K1 ACTIVE
(normal logic sense) or INACTIVE (inverted logic sense).
Default setting, P52, Bit 5: Main Contactor
Relay change-over contacts: Contact rating:-
230VAC, 3A AC11
11 - Common.
12 - Normally-closed.
14 - Normally-open
22, 24,21
Programmable Output, Relay K2.
A Bit = 1 on the parameter/bit selected by P59 makes Relay K2 ACTIVE
(normal logic sense) or INACTIVE (inverted logic sense).
Default setting, P8, Bit 3: Top of Ramp or Full Volts
Relay change-over contacts: Contact rating:
-
230VAC, 3A AC11
21 - Common. 22 - Normally-closed.
24 - Normally-open
2.7.4
Auxiliary function card Outputs - plus models only
Additional outputs available on the Auxiliary Function Card fitted within the unit.
The Auxiliary Function Card is fitted within the unit on the QFEplus.
The diagrams in section 2.5 show the location of the auxiliary function card.
Identification
Description
0V, AN1
Programmable Output, DAC OUTPUT 1.
Analogue output. A signal that represents the analogue value of the
parameter mapped from P49.
Default setting, P26:- Running Current
Voltage range:
0V to 10V. Maximum current:
10mA
0V, AN2
Programmable Output, DAC OUTPUT 2.
Analogue output. A signal that represents the analogue value of the
parameter mapped from P50.
Default setting, P22:- Delay Angle
Voltage range:
0 - 10V. Maximum current:
10mA
0V, 12V
A voltage source for use with either the 4-20mA or the 0-21V input.
Maximum current output: 100mA
32, 34, 31
Programmable Output, Relay K3.
A Bit = 1 on the parameter/bit selected by P61 makes Relay K3 ACTIVE
(normal logic sense) or INACTIVE (inverted logic sense).
Default setting, P9, Bit 0: Alarm
Relay change-over contacts: Contact rating:-
230VAC, 3A AC11
31 - Common.
32 - Normally-closed.
34 - Normally-open
42, 44, 41
Programmable Output, Relay K4.
A Bit = 1 on the parameter/bit selected by P63 makes Relay K4 ACTIVE
(normal logic sense) or INACTIVE (inverted logic sense).
Default setting, P9, Bit 1: Overload Integrating
Relay change-over contacts: Contact rating:
-
230VAC, 3A AC11
41 - Common.
42 - Normally-closed.
44 - Normally-open.
Summary of Contents for QFE Series
Page 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Page 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Page 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Page 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Page 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Page 73: ...QFE page 3 25 Applications FD841405_F...
Page 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Page 181: ...Modbus page 6 4 5MC FD510007...