Page: 44 - Installation Manual - NC-200 PB
On the model A. Set the upper negative value for the maximum
bending depth.
PAR35
Indicates the duration of the "in-position" output O29 that enables
the "BEND" foot switch.
Possible values: between 0.1 seconds and 9.9 seconds.
If = 0, the signal stays active until the pressure gage signal is received
at pin 15 of connector X2 or the programmed level is exceeded.
The output is canceled if there is a backwards movement of the X axis
in the bending stage.
PAR36
Configuration of the X axis withdrawal (retract).
0 = Move it in incremental mode in the X+ direction the distance set
by PAR37.
1 = Move it in absolute mode the value set by PAR37 .
PAR37
X axis retraction distance (incremental) or position (absolute) when
activating the I32 signal of the 37-pin connector X2 on Model "A"
or when the punch reaches the "Y=sheet thickness" position on B
and C models.
Possible values:
From 0 mm to 99999.999 mm
(From 0" to 3937").
PAR39
Analog voltage centering. Back-and-forth movement for balancing
the sign of the analog voltages.
Measure the analog voltages of this unit in both directions in any of
the ranges (fast or slow). Calculate the difference and divide by two.
Try different values of multiples of 5 mV to obtain the best balance.
For example: 6.135 and -6.120 => (0.015 difference)/2 =
0.007
Round it off to the closest value:
0.005
or
0.010