6.5.2 Settings menu S-P On (switching-on point)
Settings menu S-P On (switching-on point)
Settings menu S-P On (switching-on point)
Settings menu S-P On (switching-on point)
Settings menu S-P On (switching-on point)
The "S-P On" (Switching Point On) menu shows you the
value at which the relay is activated.
The switching-on point is specified in percent in steps of 0.1
percent. The millimetre, inch and milliampere units are
calculated and displayed for information and control.
Using the functions
[+] PLUS and
[-] MINUS
you specify the switching-on point. Confirm your selection
with RETURN [
] .
The current value must not be less than 4 mA and must not be more
than 20 mA so that malfunctions do not occur.
The following information applies only to relays K1 and K2:
For the UM-O and UM-O Ex equipment versions (overfill prevention),
you need a password for changing the switching-on point.
The range of values for these versions is between 0.1 and 98.9 percent.
The switching-on point (S-P On) is always less than the switching point
Off (S-P Off) and can never exceed this.