![fafnir SEPARIX-C L Plus Technical Documentation Manual Download Page 17](http://html1.mh-extra.com/html/fafnir/separix-c-l-plus/separix-c-l-plus_technical-documentation-manual_537398017.webp)
SEPARIX-C/-T and SEPARIX-Control CT
Page 14/37
Figure 6: SEPARIX-Control CT, terminals and "Options" DIP switch
4.2.1
Activation of SEPARIX-C
With switch 1, the SEPARIX-C L Plus interface sensor is activated. The Power LED indicates
whether the sensor is activated or deactivated (see section 4.1.1). The sensor is activated
by default.
Whenever both sensors will be deactivated, the device is no longer oper-
ational and the Power LED (see Figure 5) is OFF.
4.2.2
Activation of SEPARIX-T
With switch 2, the SEPARIX-T L Plus high-level sensor is activated. The Power LED indicates
whether the sensor is activated or deactivated (see section 4.1.1). The sensor is activated
by default.
Whenever both sensors will be deactivated, the device is no longer oper-
ational and the Power LED (see
) is OFF.
4.2.3
Relay energised
With switch 3, it is configured whether the relay is energised in case of a fault/alarm or if it
is energised in normal operation. By factory default the relay is set energised in case of a
fault/alarm.
4.2.4
Relay acknowledgeable
With switch 4 the relay is configured whether it can be acknowledged and reset in case of
a fault/alarm with the red acknowledge button. Otherwise, the relay is reset only, if the
cause of the fault/alarm is corrected. By factory default the relay is set acknowledgeable.
Summary of Contents for SEPARIX-C L Plus
Page 25: ......
Page 26: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 41: ...Blank Page...
Page 42: ...Blank Page...
Page 43: ...Blank Page...