16 <
<
<
<
L
Search in the table at TVH and THL and enter the value that is found.
found value
………………………………
If the detected value is a number, check whether the completed STL is higher or equal to the value in
the table.
Is the STL value lower as specified in the table then the installation is not possible.
Solution: Start length to low, see for the minimum length in the top row of the table.
Is the found value X, then the installation is not possible.
Solution: Change the TVH or THL.
Results
Restrictor size = Value for the comma
………………….. mm
Extra information = Value behind the comma
mark
Install the air restrictor plate, see installation manual
0,1
Install adapter 100/150 direct on top of the fire
0,2
In case of wall terminal, install adapter 100/150 before
the last bend, incase of roof terminal just before the
terminal.
0,3
In case of roof terminal (always size 100/150) install the
100/150 adapter just before the terminal.
Wall terminal 130/200
0,4
From the fire first an adjuster to 130/200 and 1 meter
130/200, after that reduce to 100/150 and everything
100/150.
0,5
Summary of Contents for Fyn 450
Page 1: ...Fyn 450 40010929 1840 Fyn 450 ENG ...
Page 2: ...1 L 1 1 1 2 1 3 1 4 1 5 1 6 2 1 2 2 2 3 ...
Page 3: ...2 L 3 1 3 2 4 0 4 1 4 2 4 3 4 4 ...
Page 15: ...14 L 12 Examples flue materials Fig 12 1 Fig 12 2 Fig 12 3 ...
Page 21: ...20 L 16Troubleshooting guide ...
Page 22: ...21 L YES ...
Page 23: ...22 L YES YES ...
Page 24: ...23 L ...
Page 25: ...24 L ...
Page 26: ...25 L 17Dimensional drawings 17 1 Fyn 450 ...
Page 27: ...26 L 17 2 Ventilation grid ...
Page 28: ...27 L 17 3 Remote access door ...
Page 29: ...28 L ...
Page 30: ...29 L ...
Page 31: ...Fyn 450 ...