LEVEL SWITCH NV-2T 

v2.1

Installation instructions 

Order. no: 13169

2012-11-07

Extronic Elektronik AB +46 (0)8-609 29 00 

1

Features

Output for 1-10 V control of fluorescent light fittings with 

• 

adjustable normal level (high level) and base level (low 

level).

Relay output for driving contactor with adjustable timer 

• 

(0–120 minutes).

Input for presence detector or logic module.

• 

Blocking input. If a light sensor is connected this can 

• 

prevent the lighting from being switched on when there is 

sufficient natural light.

Pushbutton input. If one or more pushbuttons are 

• 

connected (in parallel) the lighting can be switched on/off 

and ramped up or down manually.

SoftDim allows the lighting to be ramped up and down 

• 

gradually. The ramp-up rate is adjustable, but the dimming 

rate is fixed.

The Burn-in button delivers 100 per cent power for 100 

• 

hours

 

The  NV-2T  is  intended  for 

dynamic  lighting  control

  using 

dimmable light fittings with 1-10 V control, in order to reduce the 

lighting time for fluorescent light sources and prolong their life. It 

is used in combination with one or more presence detectors (e.g. 

PD-2200) in areas such as 

corridors

stairways

 and 

garages

See the application examples in this manual, in the “Planning 

Guide”  in  the  “Energy-saving  Detection  Technology”  manual, 

and  at  www.extronic.se,  (also  see  applications  for  NV-2T). 

Dynamic lighting control means that the output (lighting level) is 

increased to the normal lighting level (often 80 per cent) when 

presence  is  detected  in  the  premises.  When  presence  is  no 

longer detected the lighting is reduced to the base level (usually 

the lowest possible, generally 1–2 per cent).

If someone enters the premises again the lighting is ramped up 

to the normal level.

If  the  premises  remain  empty  until  the  timer  in  NV-2T  has 

counted  down  (recommended  setting  1–2  hours)  the  lighting 

is switched  off completely. The reason  why the lighting  is not 

switched off as soon as the premises are empty is that frequent 

switching causes accelerated wear to the fluorescent tubes and 

shortens their lives.

Basic operation

When someone enters the premises, the lighting is 

• 

switched on at the normal level (high level) when presence 

is detected by the presence detector.

When presence is no longer detected, the lights are 

• 

switched to the base level (low level) and the timer starts 

counting down the preset time (0–120 minutes). 

When this time has run out the lighting is switched off 

• 

completely.

When someone enters the premises while the timer is counting 

down, the lighting is switched from the base level to the normal 

level,  and  the  timer  restarts  the  countdown  when  presence 

is  no  longer  detected.  If  someone  enters  the  premises  when 

the lighting has been switched off completely, it is immediately 

switched back on at the normal level.

12 13 14 15 16

11

10

9

1

6

8

5

7

4

3

2

+

+

For  digital  regulating  of  luminaires 

with  dimmable  HF  ballasts

Extronic  AB 

• 

Stockholm 

• 

Sweden

Level  switch  NV2T-DSI

Timer  for  230  V  regulating

Current for low level regulating:   Max. 40 mA

Timer:                                             1 - 120 min.

resistive load

Power supply

:

12 - 16 VDC

Breaking capacity per 

relay output

:

5 A / 250 VAC

Min

Light 

Sensitivity

Light 

1-10 V

+9 -10

14 - 15 - 16

Timer

0

15m

30m

1h

2h

High

Level:

100%

100h

 Low

Max

Soft Dim

Min

Switch

3 - 4

1 - 2

Start

block

Max

5 - 6

7 - 8

Det.

NV-2T 

+12 VDC-

Slow

Min

Max

Max

C-NO-NC

v2.1

Fast

Auto

Timer

up to two hours

Rest

”High level”

Red knob 80%

Completely 

off

No presence

No presence

Manual

Pushbutton

”Low level”

Blue knob1%

Presence Presence

Schematic diagram

Printed circuit board with LEDs and potentiometers.

Description

Summary of Contents for NV-2T

Page 1: ...ghting is ramped up to the normal level If the premises remain empty until the timer in NV 2T has counted down recommended setting 1 2 hours the lighting is switched off completely The reason why the...

Page 2: ...D2 1 10 V NO NO NC C 12 16 VDC Steady glow when lighting set to 100 Flashing at lower levels Steady glow or flashing when relay is closed flashes when timer is counting down Green LED Green LED Red LE...

Page 3: ...switched on automatically 3 4 3 4 1 5 k 3 4 4 7 k 3 4 10 k NO 5 6 5 6 NO 4 7 k NO NC input for NC detector If a 22 k resistor is connected in series with a normally closed NC magnetic switch in a doo...

Page 4: ...ith dimmable HF ballasts Extronic AB Stockholm Sweden Level switch NV2T DSI Timer for 230 V regulating Current for low level regulating Max 40 mA Timer 1 120 min resistive load Power supply 12 16 VDC...

Page 5: ...hort circuit protection current limited Secondary Voltage 13 65V Current Max 1 5 A Primary Voltage 230 V Current Max 0 2 A 15 17 IN 230 V 10 12 UT 11 13 UT Indication of secondary voltage EXTRONIC Lev...

Page 6: ...nnecting a 10 k resistor to the detector input see the wiring diagram below Note that when power is first switched on NV 2T cannot sense the 10 k resistor at the detector input if the detector senses...

Page 7: ...ng again interrupts the burn in process During the burn in process the lighting can be switched on or off and dimmed manually Current Low level load max 100 mA Passive consumption 45 mA at 13 8 VDC Vo...